Laserfiche WebLink
SYSTEM#3—HVAC SHUTDOWN AND FIRE/SMOKE DAMPERS CONTROL <br /> A. SEQUENCE OF OPERATION: <br /> Combination fire/smoke dampers are located throughout the facility. Activation of the fire <br /> alarm system will close all combination fire smoke/damper and shut down the following listed <br /> air handling units. Upon fire alarm reset all fire/smoke dampers will open and air handiing <br /> units will automatic restart. In addition make-up air units over 2000 CFM have duct detectors <br /> which will shut down individual units when activated. <br /> Unit Designation Area Served Shut Down By Fire Duct Detector Shut <br /> Alarm Down <br /> MAU -1 2 Floor Make-Up X <br /> MAU-2 General Make-Up X X <br /> MAU-3 Welding Make-Up X X <br /> MAU-4 Sculpture Make-Up X X <br /> MAU-5 Kitchen Hood Make-Up X X <br /> B. TEST PROCEDURES: <br /> Activate fire alarm system and confirm all fire/smoke dampers close and associated air <br /> handling equipment shuts down. Reset system and confirm dampers return to operational <br /> position and air handling units automatically start and return to normal operational control. <br /> C. TEST EQUIPMENT: <br /> None <br /> D. TEST REPORT FORMAT: <br /> Record AHU shut down and closure/opening of each combination fire/smoke damper. <br /> E. TEST PARTICIPANTS: <br /> Mortenson, Elliott Contracting, Egan Mechanical <br /> Minnetonka Center for the Arts � <br /> Certificate of Occupancy Testing Manual <br />