Laserfiche WebLink
10/24/97 FRI 16:02 FA% W W GOETSCH f�019 <br /> � � Sequence Of Operation FTA <br /> Limited Service Controllers 75Q <br />� <br /> INTRODUCT/ON t M is energized.The pump motor will stop only <br /> Reference,to Wiring Schematic, Publication after the minimum run time is complete an�1 system <br /> WS750-10 will be essential in following this pressure is above the stop (high)setting cf 1 PS <br /> Seque�ce.of Operatlon. (see note 10,WS750-10). <br /> The Ilne numbers referred to in the text.appear to 3. If the jumperis removed from 12 and 13 arni placed <br /> the left side on the Wiring Schematic. between 11 and 12, minimum run time bec�ins <br /> The numbers to the �ght of the contacto�or aiter the system pressure is restored to th��stop <br /> co�trol relay coil symbols (1M, 1CR, 2CR,eta) a�e (high) setting of pressure switch 1PS. <br /> the line numbers on which the contactor or control 4. The minimum run timer may be disabled ior <br /> relay contects a�e located.A line under the number automatic start/manual stop by using�o jumpers <br /> indlcates a normally closed contact. Numbers with between terminals 11, 12 and 13,in which :,ase the <br /> no line are no�mally open contacts. Numbers above motor will run until manually shut down by <br /> which a T appears indicate a timed contact. depressing the"Stop" pushbutton. <br /> 5. When the system pressure drops to the st.art (low) <br /> ENERG/Z1NG THE CONTROLLER setting of pressure switch 1PS, control rel.�y 2CFi, <br /> 1. Close the circuit breaker by moving the handle energizes and seals itself with a normally��pen <br /> to the"On" position. NOTE-The motor may contact. 1CR deenergizes when the norm��lly <br /> give a slight bump due to the time delay closed contact of 2CR opens. 1CR contacts <br /> between closing the breaker a�d energiiing close, energizing motor contaCtor 1M. Reie�to <br /> relay 1CR.To preve�t this slight bump, "PUMP MOTOR STARTING SEpUENCE",below. <br /> depress and hold the"Stop" pushbutton until 6. The pump motor w(II ru� until: <br /> the circult breaker has closed. a. System pressure rises to the stop (high) <br /> 2. The phase monitor, FTA435, energizes, e�erglzing setting of 1 PS and; <br /> relay 4CR.The phase monitor also lights the"Power b. Minimum run timer 1TR times out oF�ening <br /> On" pilot light. 1TR contact, deenergizing relay 2CF.. <br /> 3. Upon energiZing the controller, other devices Normally closed 2CR Contacts close <br /> remain deenergizing unless there is a call to energiiing 1CR. The normally closecl 1CR <br /> start from pressure switch 1 PS, or from the contaCts open,deenergizing motor <br /> "Sta,rt" pushbuttons, or the deluge valve.The contactor 1 M,stopping the motor. <br /> deluge valve contacts are only operational if 7, When the above conditions are met and 1CF1 is <br /> the jumper hes been removed betwesn again energized, the cont�oller is i�the st��ndby <br /> terminals 8 and 10. If engaged,the Emergency cond'Rion and ready to start the pump mo�:or <br /> Run Mechanism wi�l cause the pump motor to should a start signal be received. <br /> run as described in "EMERGENCY RUN <br /> MECHANISM" below. A11?OMAT/C STAAT-MANUAL STOP <br /> 4. The controller is now ready to start the pump The pump motor is sterted by pre.ssure switcli <br /> motor shauld a start slgnal be received. 1 PS or deluge valve DV but must be stopped <br /> AUTOMAT/C START AND STOP manually with the"Stop"pushbutton.Jumpers <br /> between terminals 11, 12,and 13 must be removed <br /> 1: Pressure switch 1 PS initiates the automatic (see note 10, WS750-10). <br /> start and stop circuits for the pump motor_ �, The controlle�starts automatically when s�stem <br /> However,the pump motor stop mode is deter- pressure drops to the start(low)setting ot <br /> mined by minimum run timer 1TR and the pressure switch 1 PS control relay 2CR <br /> jumpers connected between terminals 11, 12, energizes, deenergizing 1CR a�d energiziiig <br /> a�d 13. The stop mode can function in one of motor contactor 1 M. Control relay 2CR seals <br /> three ways. The minimum run timer functlons itself. The controller will then proceed thrc�ugh <br /> in the following manner the starting sequence_ Refer to"PUMP MC)TOR <br /> 2. The factory setting includes a jumper between gTARTING SEQUENCE"below.The minimum <br /> terminels 12 and 13, and �o jumper betwee� run timer hes no effect on this operstion. <br /> terminals 11 and 12. In this mode, minimum <br /> run time begins when the pump motor contacto� <br /> I r%I'�/'�O�l�/I�C. <br /> Fire Pump Control Division <br />