Laserfiche WebLink
GeoLink Design Studio �_� � <br /> ����� <br /> Ground Source System 1 Loop Pressure Drop <br /> Freeze Protection: 25% Environo12000 (15 deg. F) <br /> i��commend�d !Vlin�m��� <br /> Unit#1 GPM PD GPM PD <br /> 5 Series Dia Length Elbows �s 15.0 �z 8.8 <br /> ND064 <br /> Unit Piping 1 10 4 16 4.4 12 2.6 <br /> Suppty Piping 1.25 10 4 34 5.8 25.5 3.5 <br /> Retum Piping 1.25 10 4 16 1.6 12 0.9 <br /> U�llt#2 GPM PD GPM PD <br /> NSW060 Dia Length Elbows �$ 15.9 13.5 9.� <br /> Unit Piping 1 10 4 18 5.4 13.5 3.2 <br /> Supply Piping 1.25 10 4 18 1.9 13.5 1.2 <br /> Retum Piping 1.25 10 4 34 5.8 25.5 3.5 <br /> Outside Dia Length Number GPM PD RE GPD PD RE <br /> Supply Line 2 100 34 4.4 10256 25.5 2.7 7692 <br /> Retum Line 2 100 34 4.4 10256 25.5 2.7 7692 <br /> Circuits 0.75 300 7 4.9 19.7 3267 3.6 11.9 2450 <br /> Sub-Circuits 0.75 0 1 0.0 0.0 0 0.0 0.0 0 <br /> System GPM & Pressure Drop 34 64.9 25.5 39.3 <br /> Flushing Requirements <br /> 28 GPM at 19.3 ft head are needed to flush the air rom this loop(IGSHPA guidelines) <br /> Loop Volume and AntiFreeze <br /> 27.2 Gallons Environol 2000 mixed with <br /> 81.5 Gallons of water will provide protection to 15 degrees F. <br /> 108.7 Gallons of mixed fluid required. <br /> Job Name: HEDEEN Project#: 1 <br />