Laserfiche WebLink
**�****** RESIDENTIAL AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE ******* <br /> FLARE HEATING & A/C INC. GOLDEN VALLEY, N�T 55427 <br /> CUSTOM 2-STORYZJONES) 11-15-95 PAGE 2 <br /> ************************* BUILDING LOADS (CONTINUED) ************************* <br /> LOAD SUMMARY FOR ZONE #2 <br /> SUPPLY CFM AT 20 DEG DT: 1, 348 CFM PER SQUARE FOOT: 0 . 638 <br /> SQUARE FT. OF ROOM AREA: 2, 112 SQUARE FOOT PER TON: 694 . 661 � <br /> TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 67 . 589 MBH <br /> TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 3 . 040 TONS <br /> TOTAL BUILDING LOAD SUMMARY <br /> SUPPLY CFM AT 20 DEG DT: 2,426 CFM PER SQUARE FOOT: 0 .438 <br /> SQUARE FT. OF ROOM AREA: 5, 534 SQUARE FOOT PER TON: 993 . 715 <br /> TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 129 . 312 MBH <br /> TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 5 . 569 TONS <br /> CALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J. <br /> ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY. <br /> BE SURE TO SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS . <br />