Rhvac I�esident�ai 8 LigM Commercial HVAC Loads � Elite Sqftware Development,Inc:
<br /> Riccar Heatlng and Cooling Wooddale Stonebay'CeMer Unit
<br /> Mdover_MN'55304 ' ,,.. , ,Pa e.:2.
<br /> 7"otal8uildin Summa Loads
<br /> Cornponent ' � : ; � ��, - Area � `.�c �S�n��� La't� � = Sen �� ���T �^
<br /> � ��,.r��` € i s r'c`"� "s'a.�k, - Rt*� �, t t �;. � "��`r.�.� i�,sRv.s�'3v ° x���lqli
<br /> Descn fion� �. � � ,�� �` = �� • � Q� � ,�. � �
<br /> r..__._ ,..�._ �� - -� � r ;��_ ��..r. i� , -�-� _..�an ' ,�Lo�S� � �s �air1� ,�: r�',�alFl,, � ��
<br /> ��';`�,�Gain;
<br /> 4A-6-d: Glazing-Double pane low-e(e=0.20 or less), 152 4,263 0 3,048 3,048
<br /> high pertormance, sliding glass door, e=Q.05 on
<br /> surface 2, any frame, outdoor insect sereen with 50%
<br /> eoverage, u-value 0.33, SHGC 0.33
<br /> Andersen: Glazing-operable window,wood sash, u-value 256.3 6,319 0 6,563 6,563
<br /> 0.29, SHGC 0.32
<br /> Andersen: Glazing-operable window,wood sash, outdoor 37.8 932 0 1,147 1,147
<br /> insect screen with 50% coverage, u-value 0.29,
<br /> SHGC 0.32
<br /> 11 N: Door-Metal-Polysfyrene Core 44.4 1;321 0 373 373
<br /> 15B0-15sf-10:Wall-Basement, , R-15 board insulation to 378 1,349 0 0 0
<br /> floor, no interior finish, 10'floor depth
<br /> 12F-Osw: Wall-Frame, R-21 insulation in 2 x 6 stud 2372.5 13,109 0 2,049 2,049
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 16B-50: Roof/Ceiling-UnderAttic with Insulation on Aftic 1718 2,921 0 1,649 1,649
<br /> Floor(also use for Knee Walls and Partition Ceilings),
<br /> Vented Attic, No Radiant Barrier, Dark Asphalt
<br /> Shingles or Dark Metal, 7ar and Gravel or Membrane,
<br /> R-50 insulation
<br /> 21A-32: Floor-Basement, Concrete slab, any thickness,2 1606 2,730 0 0 0
<br /> or more feet below grade, no insulation below floar,
<br /> any floor cover, shortest side of floor slab is 32'wide
<br /> 20P-30: Floor-Over open crawl space or garage, Passive, 100 298 0 28 2g
<br /> R-3� blanket insulation, any cover
<br /> Subtotals for structure: 33,242 0 14,857 14,857
<br /> People: 4 800 920 1,720
<br /> Equipment: 722 6,387 7,1Q9
<br /> Lighting: d 0 0
<br /> Ducfinrork: 0 0 0 0
<br /> Infiltration:Winter CFM:48, Summer CFM: 24 4,376 375 335 710
<br /> Ven#ilation: Winter CFM: 127, Summer CFM: 127 4,608 1,970 705 2,675
<br /> Exhaust: Winter CFM: 127, Summer CFM: 127
<br /> Humitlification (Wintet) 8.05 gal/day: 2,951 0 0 0
<br /> AED Excursion: 0 0 3,127 3,127
<br /> Total Building Load To#als: 45,177 3,867 26,830 30,197
<br /> Check Fi�'ures , . ,.. � � ;: ;,
<br /> Total Building Supply CFM: 1,201 CFM Per Square ft.: 0.369
<br /> Square ft. of Room Area: 3,324 Square ft. Per Ton: 1,321
<br /> Volume (ft3): 2$,942
<br /> Buildih Lo�ds�- ������° .
<br /> . . . :.: . . ,.:. :
<br /> Total Heating Required Including Ventilation Air: 45,177 Bfuh 45.177 MBH �
<br /> Total Sensible Gain: 26,330 Btuh 87 %
<br /> Total Latent Gain: 3,867 Btuh 13 %
<br /> Total Cooling Required Including Ventilation Air: 30,197 Btuh 2.52 Tons(Based On Sensible+
<br /> Latent)
<br /> Ndtes "�.y� t: ., r "�.:t ,� � �.� � ,.r ,��;:
<br /> t. s� . . .,: . , .. , ... ,.,.x
<br /> �.� _ai: .,. , - �^�;� �,..
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data
<br /> at your design conditions.
<br /> C:\...\Wooddale Center Stonebay.rh9 Friday, February 03, 2017; 3:47 PM