Laserfiche WebLink
�..� <br /> DUCT LEAKAGE TEST « V 1 �"' --�;;� ; ; � <br /> . -� I <br /> Date of Test: 3/28/17 Technician: Scott Olson <br /> Test File: Untitled <br /> Customer: Sedgwick Heating Building Address: 770 Lakeview Parkway <br /> Orono, MN 55356 <br /> Mendota Heights, MN 55120 <br /> Phone: <br /> Fax: <br /> Test Results <br /> 1. Measured Duct Leakage: 34.0 CFM/6.4 sq. in. (+/-0.0%) <br /> 2. Duct Leakage as a Percent of System Airflow: <br /> 3. Duct Leakage as a Percent of Building FloorArea: 1.0% �OSS <br /> 4. Leakage Split: Supply Side: <br /> Return Side: <br /> 5. Duct Leakage Curve: Flow Coefficient(C): 4.9 <br /> Exponent(n): 0.600 (Assumed) <br /> 6 Test Settings: Test Mode: Pressurization <br /> Test Pressure: 25.0 Pa <br /> Equipment: Series B Minneapolis Duct Blaster <br /> Test Type: Total Leakage <br /> (Duct Blaster Only) <br /> Building and System Parameters: <br /> FloorArea: 3485 sq.ft. Average Supply Operating Pressure: Pa <br /> System Airflow: Average Return Operating Pressure: Pa <br /> Supply Leakage Split: % Supply Leakage Penalty: <br /> Return Leakage Split: % Return Leakage Penalty: <br /> Percentage of Measured Leakage Connected to Outside: % (0.0 CFM) <br />