Laserfiche WebLink
SKYLI�NE FIRE PROTECTION, INC. Page 1 <br /> KINTYRE MODEL Date 6.12.2015 <br />` HYDRAULIC DESIGN INFORMATION SHEET <br /> Name - KINTRYE MODEL Date - 6.12 .2015 <br /> Location - 100 KINTRYE LANE, ORONO, MN <br /> Building - RESIDENCE System No. - 1 OF 4 <br /> Contractor - SKYLINE FIRE PROTECTION, INC. Contract No. - S-1506-13 <br /> Calculated By - J. MACK Drawing No. - 1 OF 1 <br /> Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 8'-0" <br /> OCCUPANCY - HOUSE (13D) <br /> S Type of Calculation: (X)NFPA 13 Residential ( )NFPA 13R ( )NFPA 13D <br /> Y Number of Sprinklers Flowing: ( ) 1 (X)2 ( ) 4 ( ) <br /> S ( )Other <br /> T ( )Specific Ruling Made by Date <br /> E <br /> M Listed Flow at Start Point - 18 Gpm System Type <br /> Listed Pres. at Start Point - 13.3 Psi (X) Wet ( ) Dry <br /> D MAXIMUM LISTED SPACING 16 x 20 O Deluge O PreAction <br /> E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle <br /> S Additional Flow Added - Gpm Make RELIABLE Model FIRES <br /> I Elevation at Highest Outlet - 121.5Feet Size 1/2" K-Factor 4.4 <br /> G Note: Temperature Rating 155 <br /> N <br /> Calculation Gpm Required 32 . 6 Psi Required 45.2 At Test <br /> Summary C-Factor Used: Overhead 150 Underground 150 <br /> W Water Flow Test: Pump Data: Tank or Reservoir: <br /> A Date of Test - Rated Cap. Cap. 350 GALLONS <br /> T Time of Test - @ Psi Elev. 102 <br /> E Static (Psi) - 59 Elev. <br /> R Residual (Psi) - 49 Other Well <br /> Flow (Gpm) - 55 Proof Flow Gpm <br /> S Elevation - 102 <br />-- — —------ — ---__—__-------- <br /> P Location: PUMP CURVE <br /> P <br /> L Source of Information: DATA SHEET <br /> Y <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 <br />