Laserfiche WebLink
Technical Data: KRes58 HSWX (RA3593) <br /> Nominal Max. M�' Sprinkler Sprinkler <br />• Thread Ambient K <br /> Size Orifice Pressure Tem . Factor Length Identification <br /> Inch(mm) psi(bar) °F °C Inch(mm) Number(SIN) <br /> Link '�z��NPT ��z���13) 175(12) 100 38 5.8(83.5) 2.45(62) RA3593 <br /> �RYz) <br /> Ordinary Temp.Rating Top of Deflector to Minimum <br /> Max.Coverage area Max.Spacing 165°Fl74°C <br /> Ft x Ft(m x m) Ft(m) Flow Pressure Ceiling Spacing <br /> GPM Vmin PSI bar �nch(mm) Ft(m) <br /> 18 x 20(5,5 x 6,1) 18(5,5) 29(109) 25(1,72) <br /> 20x20(6,1 x6,1) 20(6,1) 30(114) 26.8(1,85) <br /> 4 to 6(100 to 152); <br /> 16 x 22(4,9 x 7,3) 16(4,9) 33(125) 32.4(2,23) �/z(13)recessed <br /> using F2 escutcheon <br /> 16 x 24(4,9 x 7,3) 16(4,9) 38(144) 42.9(2,96) <br /> 14 x 26(4,3 x 7,9) 14(4,3) 42(160) 52.4(3,75) 8(2,4) <br /> 18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4(2,5) <br /> i6 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9(2,96) 6 to 12(152 to 305); <br /> Y2(13)Recessed <br /> 16 x 24(4,9 x 7,3) 16(4,9) 42(160) 52.4(3,6) using F2 escutcheon <br /> 14 x 26(4,3 x 7,9) 14(4,3) 46(174) 62.9(4,34) <br /> For Ceiling types refer to NFPA 13, 13R or 13D <br /> Maintenance <br /> Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res ter seal assembly shall consist of a Teflon'` coated Bel- <br /> 44 Sprinklers should be inspected and the sprinkler sys- leville spring washer with top-loaded extruded or cold <br /> tem maintained in accordance with NFPA 25, 13, 13D, head cup with 3 mm glass bulb containing no plastic <br /> and 13R. Do not clean sprinkler with soap and water,Am- parts, and having a temperature rating of [155°F (68°C)] <br /> monia or any other cleaning fluids. Remove dust by using [175°F (79°C)]. Sprinklers shall have a nominal K-factor <br /> a soft brush or gentle vacuuming. Remove any sprinkler of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome- <br /> which has been painted (other than factory applied) or plated] [White Polyester] [Special finish- specify]. Resi- <br /> damaged in any way. A stock of spare sprinklers should dential pendent sprinklers shall be Reliable Model F1 Res <br /> be maintained to allow quick replacement of damaged or 30, 49&58, SIN R3511, R3516 &R3513 (Bulletin 135). <br /> operated sprinklers. Prior to installation, sprinklers should Model Fi Res 49 & 58 Recessed Pendent/F1, <br /> remain in the original cartons and packaging until used. MOdel F1 ReS 30, 49 & 58 Recessed Pendent/ <br /> This will minimize the potential for damage to sprinklers F2� Model Fi Res 30,49&58 Recessed Pender�t/ <br /> that could cause improper operation or non-operation. �P <br /> Model F1 Res 30, 49 & 58 Pendent Sprinklers shall be [cULus ListedJ [New York City MEA <br /> Sprinkler Specifications Approved (258-93-E)] low flow residential recessed pen- <br /> Sprinklers shall be [cULus Listed] [New York City MEA dent sprinklers engineered to provide a minimum design <br /> Approved (258-93-E)] low flow residential pendent sprin- density of 0.05 gpm/ft2 over the listed coverage area. <br /> klers engineered to provide a minimum design density of Listed flows as specified by the manufacturer's technical <br /> 0.05 gpm/ft2 over the listed coverage area. Listed flows data sheets are to be used. Residential sprinklers shall <br /> as specified by the manufacturer's technical data sheets be installed in conformance with the manufacturer's in- <br /> are to be used. Residential sprinklers shall be installed stallation guidelines and the applicable installation stan- <br /> in conformance with the manufacturer's installation guide- dard. Deflector-to-ceiling distance listing shall be 1"to 8" <br /> lines and the applicable installation standard. Deflector- maximum, only for F1 Res 49. Sprinkler frame and deflec- <br /> to-ceiling distance listing shall be 1" to 8" maximum, only tor shall be of bronze frame construction having a'h" NPT <br /> for F1 Res 49. Sprinkler frame and deflector shall be of thread. Water seal assembly shall consist of a Teflon" <br /> bronze frame construction having a '/�" NPT thread. Wa- coated Belleville spring washer with top-loaded extruded <br /> *DuPont Registered Trademark <br /> 10. <br />