Technical Data: F1Res 30 CCP Pendent and Recessed Pendent/FP(SIN R3511)
<br /> � ��d Nominal Max. CCP Assembly Max. K SpNnkler
<br /> Orifice Pressure Tem .Ratin Ambierrt Tem . Length
<br /> � S� Inch mm i bar °F °C °F �C Factor �nch mm
<br /> '/z"NPT z,��,���$2� 175(12) 135 57 100 38 3.0(43.2) 2.25(57)
<br /> R'/z
<br /> Ordinary Temp.Rating Minimum
<br /> Max.Coverage area Max.Spacing 155°F/G8°C Top of Deflector to Ceiling �cing
<br /> Ft x Ft(m x m) Ft(m) Flow Pressure Inch(mm)
<br /> GPM Vmin PSI bar Ft(m)
<br /> 12 x 12 3,6 x 3,6) 12(3,6) 8(30,3) 7.0(0,48) Smooth Ceilings Yz to 1 (13 to 25.4)using CCP
<br /> � /z to 1 (13 to 25.4)using FP escutcheon.
<br /> Beamed Ceilings per NFPA 13D,13R or 13 instailed in 8(2,4)
<br /> 14 x 14(4,3 x 4,3) 14(4,3) 11 (37,8) 13.4(0,92) beams Yz to 1 (13 to 25.4)using CCP.
<br /> '/z to 1 (13 to 25.4)using FP escutcheon.
<br /> For Ceiling types refer to NFPA 13, 13R or 13D
<br /> Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516)
<br /> Nominal C�P Max.
<br /> Thread Orffice Max. Assembly Ambie�t K Sprinkler
<br /> Size Inch P�ure Temp. Temp. Factor Length
<br /> (mm) Psi(bar) Ratin Inch(mm)
<br /> �F �C �F �C
<br /> Y2"NPT
<br /> �RY2� '/,s°(11) 175(12) 135 57 100 38 4.9(70.6) 2.25(57)
<br /> Ordinary Temp.Rating Minimum
<br /> Max.Coverage Max.Spacing 155°Fl68°C Top of Deflector to Ceiling
<br /> a� Ft(m) Flow Pressure Inch(mm) Spacing
<br /> Ft x Ft(m x m) GPM L/min PSI bar Ft(m)
<br /> 12 x 12(3,6 x 3,6) 12{3,6) 13(49) 7.0(0,48)
<br /> Smooth Ceilings'/z to 1 (13 to 25.4)using
<br /> 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48) CCP.
<br /> Yz to 1 (13 to 25.4)using FP escutcheon.
<br /> 16 x 16(4,9 x 4,9) 16(4,9) 14(53) 8.2(0,56) Beamed Ceilings per NFPA 13D,13R or 13 8(2,4)
<br /> installed in beams'/z to 1 (13 to 25.4)using
<br /> 18 x 18(5,5 x 5,5) 18(5,5) 18(68,1) 13.5(0,93) CCP.
<br /> Yz to 1 (13 to 25.4)using FP escutcheon.
<br /> 20x20(6,1 x6,1) 20(6,1) 20(75,7) 16.7(1,14)
<br /> For Ceiiing types refer to NFPA 13, 13R or 13D
<br /> Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP(SIN R3513)
<br /> Nominal Max. CCP Assembly Max. Sprinkler
<br /> Thread Orifice Pressure Tem .Ratin Ambient Tem . Factor ���
<br /> Size �nch(mm) si(bar) °F °C °F °C Inch mm)
<br /> '/z"NPT ,�Z"�13) 175(12) 135 57 100 38 5.8(83.5) 2.25(57)
<br /> (RYz
<br /> Ordinary Temp.Rating
<br /> Max.Coverage , , Minimum
<br /> Max.Spacing 155 F/68 C Top of Deflector to Ceiling
<br /> a� Ft(m) Flow Pressure Inch(mm) Spacing
<br /> Ft x Ft(m x m) GPM Vmin PSI bar Ft(m)
<br /> 12 x 12(3,6 x 3,6) 12(3,6) 16(61} 7.6(0,53)
<br /> 14 x 14(4,3 x 4,3) 14(4,3) 16(61) 7.6(0,53) Smooth Ceilings Yz to 1(13 to 25.4)using CCP.
<br /> Yz to 1 (13 to 25.4)using FP escutcheon.
<br /> 16 x 16(4,9 x 4,9) 16(4,9) 16(61) 7.6(0,53) Beamed Ceilings per NFPA 13D,13R or 13 installed in beams Yz to 8(2,4)
<br /> 1(13 to 25.4)using CCP.
<br /> 18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8(0,75) Yz to 1(13 to 25.4)using FP escutcheon.
<br /> 20 x 20(6,1 x 6,1) 20(6,1) 22(83,3) 14.4(1,0)
<br /> For Ceiling types refer to NFPA 13, 13R or 13D
<br /> 5.