Final Calculations - Hazen-Williams <br /> SKYLINE FIRE PROTECTION, INC. Page 6 <br /> KINTYRE MODEL Date 6.12.2015 <br />� Hyd. Qa Dia. Fitting Pipe Pt Pt <br /> Ref. "C" or Ftng's Pe Pv *'`**""* Notes **"**" <br /> Point Qt Pf/Ft Eqv. Ln. Total Pf Pn <br /> SW3 23.03 1.101 O 5.0 10.000 27.400 K Factor=4.40 <br /> to 150.0 N 7.0 12.000 3.898 <br /> BOR3 23.03 0.0883 0.0 22.000 1.943 Vel = 7.76 <br /> BOR3 0.0 1.101 O 5.0 3.250 33.241 <br /> to 150.0 0.0 5.000 0.0 <br /> T2 23.03 0.0884 0.0 8.250 0.729 Vel = 7.76 <br /> T2 0.0 1.101 0.0 1.000 33.970 <br /> to 150.0 0.0 0.0 -0.217 <br /> T3 23.03 0.0890 0.0 1.000 0.089 Vel= 7.76 <br /> T3 0.0 1.101 30 15.0 14.000 33.842 <br /> to 150.0 0.0 15.000 0.0 <br /> RSR2 23.03 0.0883 0.0 29.000 2.562 Vel = 7.76 <br /> RSR2 0.0 1.101 O 5.0 19.000 36.404 <br /> to 150.0 2N 14.0 19.000 4.331 <br /> B2 23.03 0.0883 0.0 38.000 3.357 Vel = 7.76 <br /> 62 0.0 1.101 O 5.0 15.000 44.092 <br /> to 150.0 0.0 5.000 2.815 <br /> RSR 23.03 0.0884 0.0 20.000 1.767 Vel = 7.76 <br /> 0.0 <br /> 23.03 48.674 K Factor= 3.30 <br /> RSR 23.03 1.101 0.0 8.000 48.674 <br /> to 150.0 0.0 0.0 1.299 <br /> TEST 23.03 0.0884 0.0 8.000 0.707 Vel = 7.76 <br />-- _ _._.---------_----_.._ _ _ __ ____--.-- <br /> 0.0 <br /> 23.03 50.680 K Factor= 3.24 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 <br />