Laserfiche WebLink
Final Calculations - Hazen-Williams <br /> SKYLINE FIRE PROTECTION, INC. Page 6 <br /> KINTYRE MODEL Date 6.12.2015 <br />. <br /> Hyd. Qa Dia. Fitting Pipe Pt Pt <br /> Ref. "C" or Ftng's Pe Pv '`"*"""" Notes """*"" <br /> Point Qt Pf/Ft Eqv. Ln. Total Pf Pn <br /> SW1 16.05 1.101 2N 14.0 20.000 13.300 K Factor=4.40 <br /> to 150.0 O 5.0 19.000 3.898 <br /> BOR1 16.05 0.0453 0.0 39.000 1.765 Vel = 5.41 <br /> BOR1 0.0 1.101 O 5.0 7.000 18.963 <br /> to 150.0 0.0 5.000 0.0 <br /> RSR1 16.05 0.0453 0.0 12.000 0.544 Vel = 5.41 <br /> 0.0 <br /> 16.05 19.507 K Factor= 3.63 <br /> SW2 16.38 1.101 2N 14.0 11.000 13.868 K Factor=4.40 <br /> to 150.0 0.0 14.000 3.898 <br /> BOR2 16.38 0.0470 0.0 25.000 1.176 Vel = 5.52 <br /> BOR2 0.0 1.101 O 5.0 7.000 18.942 <br /> to 150.0 0.0 5.000 0.0 <br /> RSR1 16.38 0.0471 0.0 12.000 0.565 Vel = 5.52 <br />- -- ------- - ------__-._------ ---------.___.__-_ _ <br /> RSR1 16.05 1.101 N 7.0 14.000 19.507 <br /> to 150.0 O 5.0 12.000 4.114 <br /> 61 32.43 0.1664 0.0 26.000 4.327 Vel = 10.93 <br /> B 1 0.0 1.101 0.0 5.000 27.948 <br /> to 150.0 0.0 0.0 0.0 <br /> 62 32.43 0.1664 0.0 5.000 0.832 Vel= 10.93 <br /> B2 0.0 1.101 O 5.0 15.000 28.780 <br /> to 150.0 0.0 5.000 2.815 <br /> RSR 32.43 0.1664 0.0 20.000 3.328 Ve1= 10.93 <br />-._.__.- ------- ------------- - ---- --_-- ---- ---_-__------- <br /> 0.0 <br /> 32.43 34.923 K Factor= 5.49 <br /> RSR 32.43 1.101 0.0 5.000 34.923 <br /> to 150.0 0.0 0.0 1.299 <br /> TEST 32.43 0.1664 0.0 8.000 1.331 Vel = 10.93 <br /> 0.0 <br /> 32.43 37.553 K Factor= 5.29 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 <br />