Laserfiche WebLink
Final Calculations - Hazen-Williams <br /> SKYLINE FIRE PROTECTION, INC. Page 6 <br /> KINTYRE MODEL Date 6.12.2015 <br />' Hyd. Qa Dia. Fitting Pipe Pt Pt <br /> Ref. "C" or Ftng's Pe Pv """""*# Notes *�`***'` <br /> Point Qt Pf/Ft Eqv. Ln. Total Pf Pn <br /> PD3 16.05 1.104 0.0 14.000 13.300 K Factor=4.40 <br /> to 120.0 0.0 0.0 0.0 <br /> PD4 16.05 0.0675 0.0 14.000 0.945 Vel = 5.38 <br /> PD4 16.60 1.104 2E 5.13 8.000 14.245 K Factor=4.40 <br /> to 120.0 0.0 5.130 0.0 <br /> CPVC 32.65 0.2513 0.0 13.130 3.299 Vel = 10.94 <br /> CPVC 0.0 1.101 O 5.0 14.000 17.544 <br /> to 150.0 0.0 5.000 0.0 <br /> T3 32.65 0.1685 0.0 19.000 3.202 Vel = 11.00 <br /> T3 0.0 1.101 30 15.0 14.000 20.746 <br /> to 150.0 0.0 15.000 0.0 <br /> RSR2 32.65 0.1685 0.0 29.000 4.887 Vel = 11.00 <br /> RSR2 0.0 1.101 O 5.0 19.000 25.633 <br /> to 150.0 2N 14.0 19.000 4.331 <br /> 62 32.65 0.1685 0.0 38.000 6.403 Vel = 11.00 <br /> B2 0.0 1.101 O 5.0 15.000 36.367 <br /> to 150.0 0.0 5.000 2.815 <br /> RSR 32.65 0.1685 0.0 20.000 3.370 Vel= 11.00 <br /> 0.0 <br /> 32.65 42.552 K Factor= 5.01 <br /> RSR 32.65 1.101 0.0 8.000 42.552 <br /> to 150.0 0.0 0.0 1.299 <br /> TEST 32.65 0.1686 0.0 8.000 1.349 Vel = 11.00 <br />- ----- 0.0 <br /> 32.65 45.200 K Factor= 4.86 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 <br />