Laserfiche WebLink
+ L � <br /> � f • • ' • 1 �/ • • ' • • '� <br /> Contro! Panel Selection.Peak activity per sensor is Typically duct sensor applications require less sensitive <br /> stored to assist in evaluating specific locations.The alarm settings(such as 2.5%per foot obscurarion)due to the <br /> set point for each sensor is determined at the controt ducts being a relative dirty environment. However,the • <br /> panel,selectable as the individuai application requires. standard seven levels of TrueAlarm sensor sensitivity are <br /> Sensor Status LED.Each sensor housing's red status available for each individual sensor,ranging from 02%to <br /> LED(located on the electrical inter€ace board)pulses to 3.7/o per foot of smoke obscuration.Sensitivity is <br /> indicate communications with the panel.If the control selected and morutored at the fire atazm control panel. <br /> panel detertnines that a sensor is in alarm,or that it is - � . . - <br /> dirty or has some other type of trouble,the details aze <br /> annunciated at the control panel and that sensor housing's • Individual smoke sensitivity selection <br /> status LED will be turned on steadily.During a system • Sensitivity monitoring that satisfies NFPA 72 <br /> alarm,the control panel will control the LEDs such that sensitivity testing requirements <br /> an LED indicating a trouble will return to pulsing to help . peak value logging allows accurate analysis for <br /> identify any alarmed sensors.(Remote Status/Alarm sensirivity selection <br /> LEDs track the operation of the sensor housing LED.) • Automatic,once per minute individual sensor <br /> ' • • - - � calibration check verifies sensor integriry <br /> TrueAla�n photoelectric sensors use a stable,pulsed • Automatic environmental compensation <br /> infrared LED light source and a silicon photodiode � Smoke sensifivity is displayed in percent per foot <br /> receiver to provide consistent and accurate low power • Ability to display and print detailed sensor <br /> smoke sensing. information in plain English language <br /> • Relays of mode14098-9756 are under panel control <br /> � . . <br /> for ON,OFF,or override <br /> Duct Smoke Sensor Housing with Photoelectric Sensor* <br /> ,-_ , _. _ <br /> � Model Descnption , .` . Compatibility� - <br /> .. ... , . .., . _. , . . . <br /> Basic Duct Sensor Housing;operating power is supplied by Simplex fire alarm contro�panel modets:4100ES, <br /> 4098-9755 either IDNet or MAPNET II communications(no relay 4010ES,4008,4010,4100U,a�d tegacy products <br /> output) 4020,4100/4100+,and 4120.Also 2120 CDT if <br /> configured for MAPNET II,TrueAlarm operation <br /> Duct Sensor Housing with supervised multiple relay output, Same as above except relay operation is not <br />�_`' 098-9756 requires separate 24 VDC fire alarm power and 4081-9008 compatible with 2120 CDT; <br /> end-of-line resistor hamess;includes one 4098-9843 relay Relay output is for up to 15 total 4098-9843 Relays <br /> (additional relays are ordered separateiy) <br /> Remote LED Indicator and Test Station, Select One if Required <br /> _. . <br /> Model Description . , Compabbility _ ' Mounting; <br /> _< ___ _ . _ .._ _, <br /> 2098-9808 Red LED status indicator on single-gang stainless steel plate <br /> 4098-9755 Use single gang box, <br /> Test Station with keyswitch and red LED status indicator,on 3"H x 2"W x 2"D <br />�`�. 2098-9806 single-gang stainless steel plate; (tuming switch to"TEST" 4098-9756 �76 mm x 51 mm x 51 mm) <br /> initiates alarm for system testing) <br /> Epoxy Encapsulated Remote Relay and End-of-Line Resistor <br /> , , _ _ _ . ..�. <br /> .._ - <br /> ;. Model Descnption F ! ; ; - Compatibilityj � Location: <br /> _ . . .,_ .. _: _. . ....:.. . _ � _�._; ...�. ...- _.. , <br /> Relay;single Form C{7 A@ 120 VAC);refer to pages 3 and 4 Locate relays within 3 ft <br /> 4098-9843 for additional relay information;one included with 4098-9756; 4098-9756 only; (1 m)of device being <br /> wiring is 18 AWG(0.82 mm2)color coded wire leads connect up fo 15 �ntrolted per NFPA 72 <br /> 4081-9008 End-of-Line Resistor Hamess; 10 kS2, 1/2 W;(ref.733-894); 4098-9756 At last relay location <br /> required to supenrise remote relay coil connection <br /> 'Each duct housing includes an intemally mounted mode14098-9714 TrueAlaRn photoelectric sensor and an e�aust tube.A correctly <br /> sized sampling tube(ordered per application)is requi�ed,refer to chart below. <br /> • • . • • • • - - • - � . � � • <br /> ,. <br /> Qverall Duct dllfidth Tube Required Suggested Cut`length; <br /> _ , . , . , . _ ; <br /> 12"(305 mm) 4Q98-9854 1/2"(i2J mm)longer than duct width <br /> 13"to 23'(330 mm to 584 mm) 4098-9855 1/2"(12.7 mm)longer than duct width <br /> 24"to 46°(610 mm to 1168 mm) 4098-9856 3 in"(76 mm)longer than duct width <br /> 46"to 71"(1168 mm to 1803 mm) 098-9857 3 in"(76 mm)longer than duct width � <br /> 71"to 95"(1803 mm to 2413 mm) 4098-9858 3 in"(76 mm)longer than duct width <br /> 2 54098-0030-9 11/2012 ' <br />