Laserfiche WebLink
Issue Date: 2014/08/01 Rev No.: 0 <br /> sr�wuN <br /> INTERTEC <br /> Special Inspection Daily Report <br /> �ity of Orono, MN. Page 1 of 1 <br /> Report No.: Structural Steel#3 Date of this Report: 11-03-14 <br /> Project Name: Orono Police Department Expansion Project (No.: B14�05902 <br /> Project Address: 2730 Kelly Parkway <br /> Client: City of Orono Client Project No.: <br /> Weather: Partly Cloudy PM Mark Flynn Temperature: ° F <br /> Type of Inspection: Inspection Coverage: <br /> ❑ Continuous ❑ Masonry ❑ Rebar Placement ❑ Founclations ❑ Special Cases: <br /> � Periodic �Welding � Bolting ❑ Concrete Placement ❑ Fireproofing <br /> ❑ Piles & Piers ❑ Tendon Placement ❑ Soils <br /> Did the architect or engineer authorize changes to City-approved plans? ❑ Yes (Listed Below) ❑ No <br /> Description and location of work campleted: <br /> 1) Screen wall plate fillet welds to tube steel column and bar�oist at Roof LPvel Grid E3-�C 6 to North revised detail 11/501 <br /> bottom side now completed. No discrepancy noted <br /> 2) Outstanding discrepancy on Report#1 10-17-14 tek fasteu�ers now installed from �:hannel to light gauge metal stud <br /> Grid B-C 6 to North detail 4/S502. No discrepancy noted <br /> 3} Outstanding discrepancy on Report#1 10-17-14 tek fasteners now installed from deck support angle to light gauge <br /> metal stud Grid B-C 6 to North detail 7/S502. No discrepanc,y noted <br /> 4) Outstanding discrepancy on Report#1 10-17-14 Tube steel fillet welds�t Grid C-D 1-2 detail 1/S502 welds now <br /> installed at west cantilever end. <br /> 5) A325 1/2", 5/8"and 3/4" hexhead bofts at premanufactured building, snug tight, pliie�in dire�t contad with full nut <br /> engagement present. <br /> _ _ -------______ <br /> List tests pe�Formed: <br /> Visual <br /> • Are there any discrepancies noted from this day's observati�nns? Yes ❑ No � <br /> • Are there any outstanding discrepancies on this project? Yes ❑ No � <br /> � If yes, see attached Summary Sheet. <br /> ■ Report given to Contractor: Yes � No ❑ <br /> To the best of our knowtedge, work inspected was done in ac�ordance with the approved plans, specifications, and <br /> applicable woricmanship provisions of the current IBC, except as noted abov�e. <br /> Signed: �-��-— Graham, Dan Date: 11-03-14 <br /> Print Full Name: Daniel P. Graham I.D. No.: 1054095 S18S2 <br />