b. Busway Circuits: Install separate insulated equipment ground conductor from the <br /> ground bus to the equipment ground bar terminal on the busway. <br /> c. Nonmetallic Raceways: Instail an insulated equipment grounding con uctor in <br /> nonmetallic raceways except as otherwise indicated or unless they are desi ated for <br /> telephone or data cables. <br /> d. Metal Piping Equipment Circuits: Install a separate insulated equipment ounding <br /> conductor to electrical devices conne�ted to metallic piping systems aad opera ' g at 120 <br /> V and above, including pumps, heaters,heat tracing,and surface aatifrost hea g cable. <br /> Bond the cottductor to each such unit and to the piping. <br /> 2. Underground Conductors: Bare,tinned,stranded copper except as otherwise indicated <br /> 3. Signal and Communications: For telephone, alarm, and communication systems, pro ide a#4 <br /> AWG minimum green insulated copper conductor in racevvay from the grounding lectrode <br /> system to each terminai cabinet or central equipment location. <br /> 4. Separately derived systems required by NEC to be grounded shall be grounded as app oved by <br /> the authority having jurisdiction. <br /> 5. Installation, General: Ground electrical systems and equipment in accordance w NEC <br /> except where grounding in excess of NEC requirements is iadicated. <br /> 6. Electrical Grouad Bus: Size, location, and amangement as indicated. Space 1 inch m wall <br /> and support from wa116 inches above finished floor,except as otherwise indicated.. <br /> �• Cn'°und Rods: Locate a minimum of one-rod length from each other and at least e same <br /> distance from any other grounding electrode. Interconnect grouad rods with bare co ductors <br /> buried at least 24 inches below grade. Connect bare-cable ground conductors to gro d rods <br /> by means of exothermic welds except as otherwise indicated. Make these connections 'thout <br /> damaging the copper coating or exposing the steel. Drive rods until tops are 6 inche below <br /> finished floor or final grade except as otherwise indicated. <br /> 8. Grounding Electrode Conductor. Provide insulated copper conductor, sized as indic ted, in <br /> conduit Bond the ground conductor conduit to the conductor at each end Where a di lectric <br /> fittiag is installed in the main metallic water service pipe, connect tlie ground conducto to the <br /> street side of the fitting. Do not install a grounding jumper around dielectric fittings. B nd the <br /> ground conductor conduit to the conductor at each end. <br /> 9. Braided-Type Bonding Jumpers; Install to connect grouad clamps on water meter pi ing to <br /> electrically bypass water meters. Use elsewhere for flexible bonding and gto ding <br /> connections. <br /> I0. Route grounding and bonding conductors using the shortest and straightest paths ssible <br />. without obstcucting access or placing conductors where they may be subjected to in, <br /> impact,or damage,except as indicated. <br /> CNS/US QVEST COMMUMCATIONS GRO iNG <br /> S1�91�lA NO.96419.16 16452-3 17 D C.% <br />