Laserfiche WebLink
� � University of Minnesota Pump Selection Procedure - 10125/04 <br /> Ali boxed rectangles must be entered,the rest will be calculated. <br /> o.+s�� <br /> 1. Determine pump capacity: T���,,,T <br /> A. Gravity Distribution P�aRAM � <br /> 1.Minimum required discharge is 10 gpm <br /> 2.Ma�cimum suggested discharge is 45 gpm <br /> For other establishments at least 10%greater than the water <br /> supply rate,but no faster than the rate at which effluent will flow <br /> out of the distribution device. <br /> B. Pressure Distribution-see pressure design worksheet Son f�eatment sysrem <br /> &pant of discharge <br /> ............. <br /> Selected Pump Capac'�r: 42 gpm toioi�Pe � <br /> length <br /> ,.._,.:.,,., ,-„� 2A.elevotfon <br /> inlet difference <br /> 2. Determine Total Dynamic Head(TDH) p�pe� <br /> A. Elevation difference beiween pump and point of discharge. �- -. -- - ; <br /> 16 feet i:�� ----------------------- ------ <br /> g, Special head requirement?(See Figure-Special Head Requirements) <br /> ��feet Special Head Requirements <br /> Gravity Distribution Oft <br /> C. Friction loss in supply pipe Pressure Distribution 5ft <br /> 1. Select pipe diameter �in <br /> 2. Enter Figure E-9 with gpm(1A or B)and pipe diameter(C1) <br /> Read fiction loss in feet r 100 feet from Figure E-9 E-9 Friction Loss in Plastic Pipe <br /> Friction loss= 3.28 ff/100 ft of pipe r 100 ft <br /> nominal <br /> 3.Determine total pipe length from pump discharge to soil system discharge point. Flow Rate i diameter <br /> Estimate by adding 25 percent to pipe length for fic6on loss in fittings. m 1.5" 2.0" 3" <br /> Pi len th 6mes 1.25=equivalent pipe length 20 2.47 0.73 0.11 <br /> 240 ft x 1.25= 300 feet 25 3.73 1.11 0.16 <br /> 30 5.23 1.55 0.23 <br /> 4.Calculate total friction loss by multiplying fiction loss(C2) 35 6.96 2.06 0.3 <br /> by the equivalent pipe length(C3)and divide by 100. 40 8.91 2.64 0.39 <br /> Friction Loss= 3.28 ft/100ft X 300 ft / 100= 9.8 feet 45 11.07 3.28 0.48 <br /> 50 13.46 3.99 0.58 <br /> D. Total head requirement is the sum of elevation difference(A),special 55 4.76 0.7 <br /> head requirements(B),and total friction loss(C4). 60 5.6 0.82 <br /> 16 ft + 5 ft + 10.0 ft 65 6.48 0.95 <br /> 70 7.44 1.09 <br /> Total Head: 31.0 feet <br /> 3. Pump Selection <br /> 1.A pump must be selected to deliver at least 42 gpm(1A or B) <br /> with at least 31.0 feet of total head(2D). <br /> I hereby certify that I have completed this work in accordance with all applicable ordinances,rules and laws. <br /> � <br /> (signature) 810 (license#) (date) <br /> �� ���� <br /> Page 1 of 1 <br />