<br /> Rhvac-Residential&Light Commercial HVAC Loads ,-,,� Elite Software Development,Inc.
<br /> Heating&Cooling Two Abraham Residence �
<br /> I i Maple Grove, MN 55369 Page 4 '
<br /> - -__ ____ _
<br /> - -. _ _ -
<br /> ,S izm 2 Room Load Summary _
<br /> Htg Htg Run Run Clg Cig Clg Zone Clg Air
<br /> Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys
<br /> � No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM , li
<br /> ---Zone 1--- i
<br /> 1 Basement 3,600 51,041 1,116 10-6 554 22,073 2,599 1,087 1.25 1,293 1,087 i
<br /> Zone 1 subtotal 3,600 51,041 1,116 22,073 2,599 1,087 1,293 1,087
<br /> ---Zone 2---
<br /> 8 Upper Level 1,300 22,115 484 5-6 523 10,418 1,207 513 1.00 488 513
<br /> Zone 2 subtotal 1,300 22,115 484 10,418 1,207 513 488 513
<br /> System 2 total 4,900 78,065 1,600 32,731 4,122 1,600 1,781 1,600
<br /> System 2 Main Trunk Size: 18x17 in.
<br /> Velocity: 813 ft./min
<br /> Loss per 100 ft.: 0.047 in.wg
<br /> � Cooling System Summary
<br /> � Cooling Sensible/Latent Sensible Latent Total
<br /> Tons Split Btuh Btuh Btuh ! '
<br /> Net Required: 3.07 89°/a / 11°/a 32,731 4,122 36,853
<br /> Recommended: 3.54 77% /23% 32,731 9,777 42,508
<br /> C:\Elite\Rhvacw\Projects\Chris�Anthony Thomas HomesWbraham Residence.rhv Thu�sday, October 27, 2005, 8:18 AM