Laserfiche WebLink
� DUCTLEAKAGE TEST <br /> Date of Test: 9/17/16 Technician: Rubin <br /> Test File: 1240 arbor st orono duct blast <br /> Customer: Tim Druk Building Address: 1240 Arbor st <br /> 1240 Arbor st Orono, MN 55391 <br /> Orono, MN 55391 <br /> Phone: <br /> Fax: <br /> Test Results <br /> 1. Measured Duct Leakage: 55.7 CFM/ 10.5 sq. in. (+l-0.0 %) <br /> 2. Duct Leakage as a Percent of System Airflow: <br /> 3. Duct Leakage as a Percent of Building Floor Area: 2.7 % <br /> 4. Leakage Split: Supply Side: <br /> Return Side: <br /> 5. Duct Leakage Curve: Flow Coefficient(C): 8.1 <br /> Exponent (n): 0.600 (Assumed) <br /> 6 Test Settings: Test Mode: Pressurization <br /> Test Pressure: 25.0 Pa <br /> Equipment: Series B Minneapolis Duct Blaster <br /> Test Type: Total Leakage <br /> (Duct Blaster Only) <br /> Building and System Parameters: <br /> Floor Area: 2077 sq. ft. Average Supply Operating Pressure: Pa <br /> System Airflow: Average Return Operating Pressure: Pa <br /> Supply Leakage Split: % Supply Leakage Penalty: <br /> Return Leakage Split: % Return Leakage Penalty: <br /> Percentage of Measured Leakage Connected to Outside: % (0.0 CFM) <br />