<br /> Rhvac-Residential 8 Light Commercial HVAC Loads Elite Software Development,inc.
<br /> West Metro Mechanical Inc. Eaton 345 Forest Arms Lane,Orono,MN
<br /> Norwood,MN 55368 . _ _ _ Page6_
<br /> TotalBuilding Summary Loads
<br /> _ _ - _
<br /> Component Area Sen lat Sen Tota(
<br /> Description Quan Loss Gain Gain Gain
<br /> - ---------- ---- _---- _ -- __ _ ----
<br /> 1D-cv-o: Giazing-Double pane, operablewindow, clear, 48.3 2,288 0 1,740 1,740
<br /> vinyl frame, outdoor insect screen with 100%
<br /> coverage, light color drapes with medium weave with
<br /> 50% coverage, u-value 0.57, SHGC 0.56
<br /> 1 D-cv-o: Glazing-Double pane, operable window, clear, 438.6 20,746 0 24,090 24,090
<br /> vinyl frame, u-value 0.57, SHGC 0.56
<br /> 11P: Door-Metal- Polyurethane Core 42 1,010 0 328 328
<br /> 12F-Osw: Wall-Frame, R-21 insulation in 2 x 6 stud 1671 9,014 0 1,770 1,770
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 1560-10sf-2: Wall-Basement, , R-10 board insulation to 966.1 6,222 0 750 750
<br /> floor, no interior finish, 2'floor depth
<br /> 12F-Obw: Wall-Frame, R-21 insulation in 2 x 6 stud 292.1 1,576 0 221 221
<br /> cavity, no board insulation, brick finish, wood studs
<br /> 16B-50: Roof/Ceiling-Under Attic with Insulation on Attic 2073.3 3,441 0 2,115 2,115
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-50 insulation
<br /> 21 B-28: Floor-Basement, Concrete slab, any thickness, 2 1800 2,241 0 0 0
<br /> or more feet below grade, R-3 or higher insutation
<br /> installed below floor, any floor cover, shortest side of
<br /> floor slab is 28'wide
<br /> Subtotals for structure: 46,538 0 31,014 31,014
<br /> People: 0 0 0 0
<br /> Equipment: 0 0 0
<br /> Lighting: 0 0 0 .
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 103, Summer CFM: 54 9,113 1,073 925 1,998
<br /> Ventilation: Winter CFM: 130, Summer CFM: 130 4,606 2,572 888 3,460
<br /> Exhaust: Winter CFM: 130, Summer CFM: 130
<br /> AED Excursion: 0 0 6,263 6,263
<br /> Total Building Load Totals: 60,257 3,645 39,090 42,736
<br /> - _ _ -__
<br /> - - __ - ------------ ----
<br /> Check Fi�ures _ _ _ - - - -
<br /> -- - - --- ----- ---------- -- -------'
<br /> Total Building Supply CFM: 1,790 CFM Per Square ft.: 0.462
<br /> Square ft. of Room Area: 3,873 Square ft. Per Ton: 1,088
<br /> Volume (ft3) of Cond. Space: 34,860
<br /> _ _ -- ----- -------- _- _
<br /> Buildin� Loads ---------------------
<br /> _ _ ----- - - ------- ----:_� _-�_�_
<br /> Total Heating Required Including Ventilation Air: 60,257 Btuh 60.257 MBH �--iLL--�-_____-_____
<br /> Total Sensible Gain: 39,090 Btuh 91 %
<br /> Total Latent Gain: 3,645 Btuh 9 %
<br /> Total Cooling Required Including Ventilation Air: 42,736 Btuh 3.56 Tons(Based On Sensible+ Latent)
<br /> ---_____------ ------________�__,_�--__
<br /> Notes -_ __- __
<br /> ___..- ------ ---_- _ _------------- ____---- ---- -=---------- ----- --__.� ------------ --------
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.