AIR HANDLING UNIT SCHEDULE
<br />MODEL#: MCCB021 VOL TAGE: 200-208/60/30
<br />FAN
<br />FAN AIRFLOW (cfm)
<br />12,000
<br />EXTERNAL STATIC PRESSURE (in H20)
<br />2.00
<br />TOTAL STATIC PRESSURE (in H20)
<br />3.53
<br />SPEED (rpm)
<br />1559
<br />BRAKE HORSEPOWER (hp)
<br />11.026
<br />DX COOLING COIL
<br />COIL AIRFLOW (cfm)
<br />12,000
<br />TOTAL CAPACITY (MBh)
<br />360.0
<br />SENSIBLE CAPACITY (MBh)
<br />283.38
<br />ENTERING DRY BULB (F)
<br />80.00
<br />ENTERING WET BULB (F)
<br />67.00
<br />LEAVING DRY BULB (F)
<br />58.55
<br />LEAVING WET BULB (F)
<br />57.57
<br />SUCTION TEMPERATURE (F)
<br />45.00
<br />LIQUID TEMPERATURE (F)
<br />115.00
<br />FLUID VOLUME (gal)
<br />9.11
<br />AIR PRESSURE DROP (in H20)
<br />0.71
<br />FACE VELOCITY (ft/min)
<br />577.44
<br />FACE AREA (sq ft)
<br />20.78
<br />REFRIGERANT
<br />R22
<br />FILTERING MIXING BOX
<br />FILTER CONDITION
<br />MID-LIFE
<br />BACK OPENING AIRFLOW (cfm)
<br />12,000
<br />BACK ENTRY PRESSURE DROP (in H20)
<br />0.21
<br />TOP OPENING AIRFLOW (cfm)
<br />12,000
<br />TOP ENTRY PRESSURE DROP (in H20)
<br />0.21
<br />FRONT OPENING AIRFLOW (cfm)
<br />12,000
<br />FILTER AIRFLOW (cfm)
<br />12,000
<br />FILTER PRESSURE DROP (in H20)
<br />0.61
<br />TOTAL FILTER PRESSURE DROP (in H20)
<br />0.61
<br />MODULE TOTAL PRESSURE DROP (in H20)
<br />0.82
<br />AIR COOLED CONDENSING UNIT SCHEDULE
<br />MODEL#:RAUCC30EB
<br />ELECTRICAL
<br />UNIT OPERATING VOLTAGE RANGE
<br />180-220
<br />UNIT PRIMARY VOLTAGE
<br />200
<br />UNIT SECONDARY VOLTAGE
<br />-
<br />UNIT HERTZ
<br />60
<br />UNIT PHASE
<br />3
<br />MINIMUM CIRCUIT AMPACITY (3)
<br />148
<br />MAXIMUM OVERCURRENT PROTECTION DEVICE (2)
<br />200
<br />RECOMMENDED DUAL ELEMENT FUSE (4)
<br />175
<br />COMPRESSOR
<br />NUMBER
<br />2
<br />TONS (EA)
<br />15
<br />COMPRESSOR RATED LOAD AMPS (EA)
<br />60.5
<br />LOCKED ROTOR AMPS (EA)
<br />409
<br />OUTDOOR MOTOR
<br />NUMBER
<br />3
<br />HORSEPOWER
<br />1.0
<br />MOTOR SPEED (RPM)
<br />1140
<br />OUTDOOR MOTOR FULL LOADAMPS4.1
<br />�.5"
<br />LOCKED ROTOR AMPS
<br />20.7
<br />(HEATING EQUIPMENT SCHEDULE
<br />EXHAUST FAN SCHEDULE
<br />TAG
<br />MANUFACTURER
<br />MODEL
<br />CFM
<br />- SP
<br />FRPM
<br />MOTOR DATA
<br />SIZE HP.
<br />VOLTAGE I
<br />ENCLOSURE
<br />RPM
<br />WINDINGS
<br />Y
<br />.5"
<br />208/60/30
<br />.75 GAS 172,800
<br />10"
<br />420
<br />1,400
<br />2
<br />-
<br />ODP
<br />1725
<br />1
<br />EF -1
<br />GREENHECK
<br />CWB-121-5
<br />1,700
<br />�.75"
<br />1,717
<br />1/2 HP
<br />115/60/10
<br />EF -2
<br />BROAN
<br />QTXE-150
<br />150
<br />�.5"
<br />-
<br />FRAC.
<br />115/60/10
<br />-
<br />-
<br />-
<br />EF -3
<br />BROAN
<br />QTXE-150
<br />150
<br />-.5"
<br />-
<br />FRAC.
<br />115/60/10
<br />-
<br />-
<br />-
<br />EF -4
<br />BROAN
<br />QTXE-150
<br />150
<br />.5"
<br />-
<br />FRAC.
<br />115/60/10
<br />-
<br />-
<br />-
<br />EF -5
<br />BROAN
<br />QTXE-150
<br />150
<br />.5"
<br />-
<br />FRAC.
<br />115/60/10
<br />-
<br />-
<br />-
<br />EF -6
<br />GREENHECK
<br />SB -30
<br />8,100
<br />.5"
<br />-
<br />1.5
<br />208/60/103
<br />-
<br />-
<br />-
<br />MAKE UP AIR SCHEDULE
<br />TAG
<br />MANUFACTURER
<br />MODEL
<br />CFM
<br />SP EXT.
<br />ELECTRICAL DATA HEATING SECTION
<br />RATING
<br />HP TYPE TOTAL CAP.
<br />MUA-1
<br />RUPP
<br />R1D.250-G10
<br />1,800
<br />Y
<br />.5"
<br />208/60/30
<br />.75 GAS 172,800
<br />TAG IMAN UFACTURERI MODEL SIZE I INPUT I OBTPUT
<br />BOILER
<br />SLANT FIN GG300ECN
<br />2 0 300,000 AGA INPUT- NATURAL GAS FIRED 600,000
<br />1 480,000
<br />PUMPS
<br />BELL & GOSSETT
<br />BG -212
<br />FRAC. HP - 50 GPM - ® 35' HEAD
<br />AIR CONTROL I
<br />BELL & GOSSETT
<br />BG-2121AS
<br />AIR SEPARATOR R-4"
<br />EXPANSION TANKS I
<br />BELL & GOSSETT
<br />AM -60
<br />PRESSURIZED VERTICAL TANK
<br />15000 GENERAL PROVISIONS
<br />15300 INSULATION
<br />VA V BOX ,SCHEDULE
<br />TAG
<br />MANUFACTURER
<br />INLET SIZE
<br />CFM MIN
<br />CFM MAX
<br />HOT WATER COIL
<br />ROWS BTUH
<br />VAV-1
<br />NAILOR
<br />10"
<br />360
<br />1,200
<br />2 1
<br />-
<br />VAV-2
<br />NAILOR
<br />10"
<br />420
<br />1,400
<br />2
<br />-
<br />VAV-3
<br />,'JAILOR
<br />10"
<br />225
<br />750
<br />2
<br />-
<br />VAV-4
<br />NAILOR
<br />10"
<br />225
<br />750
<br />2
<br />-
<br />VAV-5
<br />NAILOR
<br />13x10 OVAL
<br />420
<br />1,400
<br />2
<br />-
<br />VAV-6
<br />NAILOR
<br />24x16
<br />1500
<br />5,035
<br />2
<br />-
<br />VAV-7
<br />NAILOR
<br />16x10 OVAL
<br />540
<br />1,800
<br />2
<br />-
<br />VAV-8
<br />NAILOR
<br />10"1
<br />210
<br />700
<br />2
<br />-
<br />ELECTRIC ENTRY WAY HEATER SCHEDULE
<br />TAG MANUFACTURER MODEL VOLTAGE KW AMP ROUGH OPENING
<br />EH -1 QMARK 3UF60 208/10 3 14.5 18 1/4"H x 14 3/8"W
<br />1.) PROVIDE ALL WORK AND MATERIALS AS REQUIRED IN FULL ACCORDANCE WITH STATE AND LOCAL CODES,
<br />U
<br />ORDINANCES AND/OR AGENCIES HAVING JURISDICTION OVER THE WORK.
<br />1.)
<br />INSULATION SHALL HAVE COMPOSITE FIRE AND SMOKE HAZARD RATING AS TREATED BY PROCEDURE ASTM.
<br />2.) FURNISH ALL LABOR AND MATERIALS TO PROVIDE A COMPLETE, FUNCTIONING HVAC INSTALLATION.
<br />E-84, NFPA 225 AND UL 723 NOT EXCEEDING FLAME SPREAD OF 25 AND SMOKE DEI/ELOPED OF ,50.
<br />3.) TAKE OUT ALL NECESSARY PERMITS, LICENSES AND CERTIFICATES AND PAY ALL FEES.
<br />COVER PIPING WITH PRE MOLDED FIBERGLASS INSULATION, HAVING AN ALL-PURPOSE VAPOR BARRIER JACKET.
<br />4.) VISIT THE SITE AND BECOME FAMILIAR WITH ALL CONDITIONS SURROUNDING THE WORK.
<br />L LJ
<br />COVER FITTINGS, VALVES, AND FLANGES WITH PRE FORMED RIGID SECTIONAL FIBERGLASS INSULATION
<br />5.) DRAWINGS ARE DIAGRAMMATIC ANG INTENDED TO SHOW APPROXIMATE LOCATIONS UNLESS SPECIFICALLY
<br />EXTERNAL INSULATION WHERE DUCTWORK IS CONCEALED SHALL BE FIBERGLASS BLANKET, MINIMUM 1-1/2" THICK
<br />DIMENSIONED. COORDINATE THE WORK WITH EXISTING CONDITIONS AND OTHER TRADES TO AVOID CONFLICT.
<br />2.)
<br />OUTSIDE AIR DUCTWORK SHALL BE 2" BLANKET, MIN/MUM 1 PCF DENSITY.
<br />3.)
<br />SUPPLY AIR WITHIN 20' OF AIR HANDLERS UNIT, 1 " DUCT LINER
<br />4.)
<br />EXPOSED RECTANGULAR EXHAUST AND RELIEF AIR DUCTWORK WITHIN 10 FEET OF EXTERIOR WALL OR ROOF-
<br />I`o
<br />2- 3/4 PCF FIBERGLASS BLANKET WHERE CONCEALED
<br />15100 STAR T -.[.I -P OF S YSTEMS G UA-RANTEf
<br />Z
<br />AND INSTRUCTIONS
<br />�
<br />U
<br />15600 HLA TING, VL'NTILA TING AND AIR CONDITIONING
<br />1.) CONTR4CTORS SHALL GUARANTEE ALL WORK AND MATER/ALS FOR A PERIOD OF ONE YEAR.
<br />LJJ
<br />2.) THE OPERATING PERSONNEL SHALL. BE FULLY INSTRUCTED BY THE CONTR4CT0R /N THE OPERATION OF EACH
<br />O
<br />O
<br />Z
<br />MECHANICAL SYSTEM
<br />1.)
<br />CONSTRUCT ALL DUCTWORK IN ACCORDANCE WITH SMACNA STANDARDS. EXTEND
<br />LTJ
<br />DUCTWORK SUBSTANTIALLY AS SHOWN ON DRAWINGS. INSTALL ADJUSTABLE QUADRANT DAMPERS
<br /><z
<br />IN ALL BRANCH DUCTS. SEAL ALL DUCTWORK /N ACCORDANCE WITH SMACNA STANDARDS. • ABOVE 2 INCH
<br />U
<br />(f)
<br />W.G. STATIC PRESSURE - SEALS CLASS W' BETWEEN 1 /NCH AND 2 /NCH W.G. - SEAL CLASS "B';• LESS THAN 1 INCH W.G.
<br />U
<br />�Oci:�
<br />-SEAL CLASS "C" DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE DIMENSIONS. INCREASE AS NECESSARY TO
<br />jJ
<br />15200 BASIC MA TRIALS AND Mf THOD'I ]� IL ING
<br />ACCOMMODATE DUCT LINING WHERE SPECIFIED
<br />m
<br />O
<br />FLEXIBLE DUCTWORK SHALL BE. THEMAFLEX 3M OR EQUAL MAXIMUM FLEXIBLE DUCT LENGTHS SHALL BE 5 FT.
<br />1.) ALL PIPING MATER/AL AND METHODS OF CONSTRUCTION AND WORKMANSHIP SHALL BE PROVIDED AS PER THE
<br />2.)
<br />PROVIDE UL LABELED COMBINATION SMOKE AND FIRE DAMPERS WHERE SHOWN, MULTIBLADE AND DAMPER MOUNTED
<br />REQUIREMENTS OF GOVERNING CODES AND REGULATIONS
<br />IN ACCORDANCE WITH NFPA 90A.
<br />2.) STEAM, CONDENSATE, AND CHILLED WATER
<br />3.)
<br />GRILLES, REGISTERS AND DIFFUSERS: REFER TO SCHEDULE ON DRAW/NG, FINISH SHALL BE WHITE BAKED ENAMEL.
<br />A. SCHEDULE 40 WITH EXTRA HEAVY FITTINGS
<br />4.)
<br />DAMPERS: PROVIDE MANUAL VOLUME DAMPERS WHERE NOTED
<br />B. CONDESATE DRAINS
<br />d-
<br />O
<br />* TYPE "L" OR "M" HARD COPPER
<br />U
<br />3.) VALVES
<br />Z
<br />A. ACCEPTABLE MANUFACTURER
<br />15700 TESTING AND BALANCING
<br />1. GATE OR GLOBE VALVES: NIBCO OR EQUAL
<br />Q
<br />2. BALL VALVES: MATR4FLEX OR EQUAL
<br />J
<br />1.)
<br />BALANCE AIR SYSTEMS SO AS TO PRODUCE AIR VOLUMES NOTED ON DR4W/NGS
<br />� J �
<br />GILBERT MECHANICAL
<br />CONTRACTORS
<br />4451 WEST 76TH STREET
<br />MINNEAPOLIS, MN 55435
<br />(952) 835-3810 OFFICE
<br />(952) 835-4765 FAX
<br />HIS DRAWING IS THE EXCLUSIVE
<br />'ROPERTY OF GILBERT
<br />MECHANICAL, AND WAS PREPARED
<br />OR THE EXCLUSIVE USE OF
<br />31LBERT MECHANICAL FOR THE
<br />SERVICES PERFORMED BY GILBERT
<br />MECHANICAL. NO USE,
<br />REPRODUCTION, OR DUPLICATION
<br />)F THIS DRAWING, IN PART OF
<br />NHOLE MAY BE MADE WITHOUT
<br />NRITTEN CONSENT OF GILBERT
<br />MECHANICAL.
<br />I HEREBY CERTIFY THAT THIS PLAN
<br />WAS PREPARED BY ME OR UNDER
<br />MY DIRECT SUPERVISION AND THAT
<br />I AM A DULY REGISTERED
<br />ENGINEER UNDER THE LAWS OF
<br />THE STATE OF MINNESOTA.
<br />Q: ;
<br />..,.---
<br />7
<br />ErNGINE'ER'S SIG E
<br />MINNESOTA REG #
<br />DATE: NO: REVISIONS:
<br />DATE: 8/2/04
<br />DRAWN BY: RRM
<br />DESIGNED BY: JG
<br />SCALE: NO SCALE
<br />JOB NUMBER: 04-1304-80 I
<br />SHEET
<br />M5 OF 5
<br />i
<br />U
<br />Z
<br />L LJ
<br />U
<br />LTJ
<br />r0
<br />Zr-1Q
<br />Z
<br />I`o
<br />LTJ
<br />_j
<br />Z
<br />(Ji
<br />�
<br />U
<br />Q
<br />LJJ
<br />L1J
<br />O
<br />O
<br />Z
<br />ZO
<br />_JD
<br />LTJ
<br />i --
<br /><z
<br />J
<br />U
<br />(f)
<br />D
<br />U
<br />�Oci:�
<br />Q
<br />Q
<br />m
<br />O
<br />F-
<br />LL
<br />Z
<br />�
<br />U
<br />O
<br />d-
<br />O
<br />U
<br />0f
<br />Z
<br />Q
<br />J
<br />ry
<br />Q
<br />_
<br />DATE: NO: REVISIONS:
<br />DATE: 8/2/04
<br />DRAWN BY: RRM
<br />DESIGNED BY: JG
<br />SCALE: NO SCALE
<br />JOB NUMBER: 04-1304-80 I
<br />SHEET
<br />M5 OF 5
<br />i
<br />O
<br />to
<br />L LJ
<br />=
<br />U
<br />Z
<br />O
<br />Z
<br />U
<br />�
<br />U
<br />U
<br />LJJ
<br />L1J
<br />.,
<br />-�
<br />_JD
<br />C)
<br />i --
<br /><z
<br />cif,
<br />CI -O
<br />�Oci:�
<br />Q
<br />U
<br />O
<br />o�
<br />LTJ
<br />'-L-'
<br />F -
<br />(n
<br />DATE: NO: REVISIONS:
<br />DATE: 8/2/04
<br />DRAWN BY: RRM
<br />DESIGNED BY: JG
<br />SCALE: NO SCALE
<br />JOB NUMBER: 04-1304-80 I
<br />SHEET
<br />M5 OF 5