PC Exhibit J <br /> Melanie Curtis <br /> From: James Van Eyll [JVaneyll@ci.long-lake.mn.us] <br /> Sent: Thursday, June 10, 2010 9:13 AM . <br /> To: Melanie Curtis <br /> Subject: RE: Ecumen Senior Living <br /> Hi Melanie, . <br /> Here are our comments. <br /> 1. The over hang/canopy needs to be a minimum of 13'6" above grade. We will not be able to turn any of our <br /> larger trucks around in the parking lot at the 9'6" as stated on the plans. If they don't want to raise the canopy <br /> then.they will need to supply us with a better turn around for our apparatus. <br /> 2. It appears that a 12"water main is supplying the water,so we should have the minimum fire flow satisfied. <br /> 3. The plans did not show a sprinkler riser room anywhere. I would like to see where they plan to place that room <br /> and then where our fire department connection would be located. <br /> 4. The fire department connection will require a fire hydrant within 50'of it. <br /> 5. There will also need to be 2 more fire hydrants and I would like to be involved with the placement of those <br /> hydrants,so that we don't block access to the building. <br /> 6. We are happy to see that the building will be fully sprinklered and a Type V-A construction. <br /> 7. Since the building is equipped with fire sprinklers,we will not require access to the backside of the building but <br /> we would like to see a sidewalk along the west side of the building. <br /> This looks like a great plan from the fire stand point. Hopefully everything works with it. �` <br /> Thanks, <br /> James Van Eyll <br /> Chief,Long Lake Fire � <br /> 450 Virginia Avenue <br /> PO Box 606 <br /> Long Lake,MN 55356 <br /> 952-473-9701 office <br /> 952-367-6447 cell <br /> Please consider the environment before printing this email . <br />