<br /> ; ; System 1 Main_Floor Summary Loads _ _ _ __ _ _i
<br /> ---_ _ ___ --_ -----_ ----__._ _
<br /> � Camponent Area Sen Lat Sen Tatal
<br /> � �-----
<br /> , �Descnption __ __ Quan Loss Gain Gain Gain '
<br /> _ _ _--- -- _ _ -- - -- - - _----- -- ---
<br /> � Keyland Window: Glazing-Keyland Window, u-value 542.8 15,044 0 13,000 13,000
<br /> 0.33, SHGC 0.33 '
<br /> Keyland Patio: Glazing-Keyland Ratio, u-value 0.3, SHGC 186 4,688 0 6,803 6,803 ;
<br /> I� 0.37
<br /> 71P: Door-Metal-Polyurethane Core 63 1,536 0 567 567
<br /> 15B13-Ow-8:Wall-Basement, ,framing with R-13 sill to 903 4,085 0 144 144 ;
<br /> ' floor in 2 x 4 cavity, core, no board insulation, plus
<br /> interior finish,wood studs, 8'floor depth ,
<br /> 12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 4429.9 25,303 0 6,748 6,748
<br /> , cavity, no board insulation, siding finish,wood studs �
<br /> 166-4�4: Roof/Ceiling-Under Attic with Insulation on Attic 2772.1 5,122 0 3,355 3,355 �
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings),Vented Attic, No Radiant Barrier, Dark �
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or '
<br /> Membrane, R-44 insulation
<br /> ! 21A-20: Floor-Basement, Concrete slab, any thickness, 2 1844.9 4,184 0 0 0 ,
<br /> or more feet belaw grade, no insulation below floor, �
<br /> any floor cover, sho�test side of floor slab is 20'wide i
<br /> ! 20P-38: Floor-Over open crawl space or garage, Passive, 583.7 1,471 0 263 263
<br /> � R-38 blanket insulation, any cover
<br /> Subtotals for structure: 61,433 0 30,880 30,880 f
<br /> ' People: 7 1,400 1,610 3,010 �
<br /> Equipment: 1,200 1,200 2,400 i
<br /> ; Lighting: 0 0 0 ',
<br /> � ouctwor�: o 0 0 0 '
<br /> , Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0 :
<br /> Ventilation: Winter CFM: 250, Summer CFM: 250 22,412 3,928 5,336 9,264 ,
<br /> AED Excursion: 0 0 278 278 '
<br /> System 1 Main Floor Load Totals: 83,845 6,528 39,305 45,833
<br /> -- ---_ . _ - _ _
<br /> _ --
<br /> 'Check�i ures ___
<br /> �--- 9- _ _ _�
<br /> -_- - ____ -- -_ -- -- -
<br /> Supply CFM: 1,591 CFM Per Square ft.: 0.266 i
<br /> Square ft. of Room Area: 5,991 Square ft. Per Ton: 1,569 '
<br /> Volume (ft3}of Cond. Space: 54,666 j
<br /> _ _ _.__ - _._
<br /> _.__ . ,
<br /> ,.S�stem Loads _
<br /> - -�._ ---- -- _ _ _ ____ -- - - -- _. ._ . _ ;
<br /> Total Heating Required Including Ventilatian Air: 83,845 Btuh 83.845 MBH
<br /> Total Sensible Gain: 39,305 Btuh 86 % +
<br /> Total Latent Gain: 6,528 Btuh 14 % �
<br /> ! Total Cooling Required Including Ventilation Air: 45,833 Btuh 3.82 Tons(Based On Sensible+Latent) �
<br /> _ . _ - - --_ .
<br /> ,� [Notes _ ___ _- ___ _ � I
<br /> _ __--_- ---- --- -- __-------------- _------ -------- -_
<br /> j Rhvac is an ACCA approved Manual J and Manual D computer program. '
<br /> ; Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> I All computed results are estimates as buiiding use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads accvrding to the manufacturer's performance data at
<br /> your design conditions.