<br /> ' Rhvac-Residential 8 Light Commercial HVAC Loads ,, Elite Software Development,Inc.'
<br /> Sabre Plumbing&Heating � Sundberg-1161 Elmwood Ave Orono'
<br /> Plymouth,MN 55447 ___ Page 4
<br /> System 1 Summary Loads _ __
<br /> Component Area Sen Lat Sen Totall
<br /> Descnption ____ _ _ _____ Quan _______ Loss Gain_ Gain Gain �
<br /> LOW EE: Glazing-Builder Grade Low E Windows& 539.8 14,222 0 12,632 12,632
<br /> Sliding Door.33 U value .33 SHGC, u-value 0.31,
<br /> SHGCO29
<br /> 11J: Door-Metal- Fiberglass Core 61.3 3,128 0 957 957
<br /> 12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 2629.9 15,201 0 3,113 3,113
<br /> cavity, no board insulation, siding finish,wood studs
<br /> 15A-10sffc-4: Wall-Basement, concrete block wall, R-10 566 2,407 0 0 0
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core,4'floor depth
<br /> 166-50: Roof/Ceiling-UnderAtticwithlnsulationonAttic 1243.7 2,114 0 1,244 1,244 '
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings),Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-50 insulation
<br /> 21A-32: Floor-Basement, Concrete slab, any thickness, 2 1199.9 2,040 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 32'wide
<br /> ', 20P-30: Floor-Over open crawl space or garage, Passive, 22 65 0 8 8 '
<br /> ' R-30 blanket insulation, any cover
<br /> ' Subtotals for structure: 39,177 0 17,954 17,954
<br /> People: 6 1,200 1,380 2,580
<br /> Equipment: 448 2,310 2,758
<br /> Lighting: 0 0 0
<br /> Ductwork: 2,611 164 984 1,148 ',
<br /> Infiltration: Winter CFM: 207, Summer CFM: 188 18,788 3,963 3,013 6,976 '
<br /> Ventilation: Wnter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> Exhaust: Winter CFM: 180, Summer CFM: 180
<br /> Humidification (Winter)4.98 gal/day : 1,826 0 0 0
<br /> AED Excursion: 0 0 2,785 2,785
<br /> System 1 Load Totals: 62,402 5,775 28,425 34,201
<br /> _ _ _ --_ . __ _ _ --
<br /> Check Figures _ � '
<br /> - _ _ . _ ___
<br /> Supply CFM: 1,332 CFM Per Square ft.: 0.447
<br /> Square ft. of Room Area: 2,978 Square ft. Per Ton: 1,045
<br /> Volume(ft3)of Cond. Space: 26,243
<br /> ___ __
<br /> _
<br /> System Loads_ . _
<br /> --- _ - -- _ --- �
<br /> Total Heating Required Including Ventilation Air: 62,402 Btuh 62.402 MBH
<br /> Total Sensible Gain: 28,425 Btuh 83 %
<br /> Total Latent Gain: 5,775 Btuh 17 %
<br /> Total Cooling Required Including Ventilation Air: 34,201 Btuh 2.85 Tons(Based On Sensible+Latent)
<br /> _ __
<br /> Notes _ _ __--_
<br /> _-- - ._- -_ __- _ __ --_ i
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions. '