<br /> �tHVAC-Residerrtial&Light Commercial HVAC Loads Program r� EIiEc Softwar+�Development,fnc. ';
<br /> • Ditter,Inc. � �bSt '
<br /> Namel,MN 55340-9691 �' p�ge 7 i
<br /> � _ ,. . .. . '<_ _ _ '
<br /> j, _ _ . ,,---,-.- ,-_..—_,-�--.___.,_..__r'T -
<br /> System #1 Zone#1 Summa'ry Loads , ���� �` ` " �� � �� ,'
<br /> � _
<br /> Component Area Sen. Lat. 5en. Total
<br /> Description Quan Loss Gain Gain Gain
<br /> 3E Window Double Pane Low Emit TIM Frame 130 4,772 0 5,184 5,184
<br /> i 8M Glass Door pouble Clear Glass Wood Frame 35 1,774 0 1,330 1,330
<br /> i 12H Wail R-19 + 1/2" Gypsum Board(R-0.5) 1,959 10,813 0 2,775 2,775
<br /> 22D Slab on Grade 2" Edge Insulation(R-11) 236 4,560 0 0 0
<br /> � Subtotals for structure: 2,360 21,919 0 9,289 9,289
<br /> ' Active People: 4 0 920 1,200 2,120
<br /> Inactive People: 0 0 0 0 0
<br /> Appliances: 0 0 0 0 0
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0 0
<br /> Infiltration: Winter CFM: 67.2, Summer CFM: 44.8 165 6,799 1,096 985 2,081
<br /> Ventilation: Winter CFM: 8.4, Summer CFM: 10.3 � 0 n/a n/a n/a n/a
<br /> � Sensible Gain Total: 11,474
<br /> � Temperature Swing Multiplier: X1.00
<br /> , Zone Load Totals: 28,718 2,016 11,474 13,490
<br /> ' _ __ ..._. _. '. ... - -
<br /> __ _.. _ _
<br /> � Check Figures � ��� ,� � , �' , �,�
<br /> �
<br /> ; Supply CFM: 413 CFM per square foot: 0.188 i
<br /> � Square feet of room area: 2,196 Square feet per ton: 1,833.188
<br /> _ _. _ . _ , . . _ . _ . . . ._ __ � , , _ .
<br /> Zane Loads , �
<br /> _ , � ' ,: , ' .
<br /> Total heating required with outside air: 28,718 Btuh 28.718 MBH
<br /> Total sensible gain: 11,474 Btuh 85 %
<br /> Total latent gain: 2,016 Btuh 15 %
<br /> Total cooling required with outside air: 13,490 Btuh 1.124 Tons (based on sensible + latent)
<br /> 1.198 Tons (based on 77% sensible capacity)
<br /> �
<br /> �
<br /> Monday,November0l, 1999