<br /> RHVAC-Residential&Light Commercial HVAC Loads Program � Elite Software Development,Inc.
<br /> ' Ditter,Inc. KROLCZYK '
<br /> Hamel,MN 55340-9691 05-12-2004 Page 3 ,
<br /> �ystem #1 Zone#1 Summary Loads
<br /> , Component Area Sen. Lat. Sen. Total '
<br /> Description Quan Loss Gain Gain Gain
<br /> , _ - _ _ __ __ _ - _
<br /> , 3E Window Double Pane Low Emit TIM Frame 458 16,812 0 20,798 20,798 '
<br /> 8M Glass Door pouble Clear Glass Wood Frame 140 7,097 0 5,439 5,439
<br /> , 11 B Door Metal Fiberglass Core & Storm 21 709 0 205 205
<br /> 12H Wall R-19 + 1/2" Gypsum Board(R-0.5) 1,592 8,788 0 2,541 2,541
<br /> 161 Ceiling R-44 Insulation 2,464 5,214 0 2,664 2,664
<br /> - - - _
<br /> Subtotals for structure: 4,675 38,620 0 31,647 31,647
<br /> Active People: 6 0 1,380 1,800 3,180
<br /> Inactive People: 0 0 0 0 0
<br /> Appliances: 0 0 0 1,200 1,200
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0 0
<br /> Infiltration: Winter CFM: 184.9, Summer CFM: 92.4 619 18,152 2,590 2,269 4,859
<br /> Ventilation: Winter CFM: 17.7, Summer CFM: 0.0 0 n/a n/a n/a n/a
<br /> ' Sensible Gain Total: 36,916
<br /> ', Temperature Swing Multiplier: X1.00
<br /> Zone Load Totals: 56,772 3,970 36,916 40,886
<br /> Check Figures �,
<br /> _ _ . __
<br /> Supply CFM: 1,729 CFM per square foot: 0.702 ��
<br /> Square feet of room area: 2,464 Square feet per ton: 623.719 '�
<br /> Zone Loads _ _ __ _ _ _ _ _ '
<br /> _ _ _ _ _ _ _ _ _ . �
<br /> Total heating required with outside air: 56,772 Btuh 56.772 MBH
<br /> Total sensible gain: 36,916 Btuh 90 % ���
<br /> Total latent gain: 3,970 Btuh 10 % '
<br /> Total cooling required with outside air: 40,886 Btuh 3.407 Tons (based on sensible + latent) ',
<br /> 3.950 Tons (based on 77% sensible capacity) '
<br /> � _ - -_ _ _ -_ _ ----__ _ ___ . _ _ -- -_ _ --
<br /> Monday,May 17,2004