Laserfiche WebLink
Rhvac-Residential 8 Light Commercial HVAC Loads Elite Software Development,Inc. �I <br /> West Metro Mechanical Inc. � M8�M Orono Model Home <br /> Nonv_ood MN 55368 Page 12 ' <br /> Detailed Room Loads - Room 5 - Main Level, Pantry, Enfry, W.1. Closet (Average <br /> Load_Procedure) <br /> __- <br /> _ --_ <br /> General <br /> I Calculation Mode: Htg. &clg. Occurrences: 1 <br /> Room Length: 12.0 ft. System Number: 1 <br /> Room Width: 23.5 ft. Zone Number: 1 <br /> Area: 282.0 sq.ft. Supply Air. 37 CFM , <br /> Ceiling Height: 9.1 ft. Supply Air Changes: 0.9 AC/hr <br /> Volume: 2,561.5 cu.ft. Req. Vent. Cig: 0 CFM <br /> Number of Registers: 1 Actual Winter Vent.: 10 CFM , <br /> I Runout Air: 37 CFM Percent of Supply.: 28 % <br /> Runout Duct Size: 4 in. Actual Summer Vent.: 6 CFM <br /> Runout Air Velocity: 422 ft./min. Percent of Supply: 15 % <br /> ', Runout Air Velocity: 422 ft./min. Actual Winter Infil.: 18 CFM <br /> ' Actual Loss: 0.198 in.wg./100 ft. Actual Summer Infil.: 10 CFM <br /> — --- -- — <br /> — -- — ---- --- <br /> Item Area -U- Htg Sen Clg Lat Sen '' <br /> Descri tion _ __ .___ Quantity Value __.___HTM__ ___ __Loss HTM Gain Gain <br /> W-Wall-12F-Osw 12 X 9.1 109 0.065 5.3 574 1.1 0 115 <br /> S-Part-5°/5°-12F-Osw 23.5 X 9.1 198.7 0.065 0.3 65 0.3 0 65 <br /> E-Wall-12F-Osw 12 X 9.1 85 0.065 5.3 448 1.1 0 90 <br /> E-Door-11 D 3 X 8 24 0.390 31.6 758 10.5 0 253 <br /> S-Gls-1 F-hw-o in partition 14.8 _ 0.440 _ 2.2 33 2.2 __ __ _0 33 <br /> , Subtotals for Structure: 1,878 0 556 <br /> ' Infil.: Win.: 17.8, Sum.: 9.5 431 3.558 1,535 0.375 188 162 <br /> � AED Excursion: 68 <br /> � Room Totals: 3,413 188 786 <br /> � _ __ — -- -- <br /> C:\...\M&M Orono Model Home.rh9 Sunday, March 20, 2016, 9:53 AM <br />