<br /> RHVAC-Residential&Light Commercial HVAC Loads Program � Elite Software Development, Inc.
<br /> . A-ABC Appliance&Heating � Stephanie Grand
<br /> Minneapolis, MN 55408 08/13l96 Page 3
<br /> _-- _
<br /> Total Building Summary Loads
<br /> ' - --- __ _
<br /> �'I Component Area Sen. Lat. Sen. Total ''�
<br /> Description Quan Loss Gain Gain Gain '
<br /> 3A Window Double Pane Clear Glass Wood Frame 76 3,852 0 1,748 1,748
<br /> 5A Window Triple Pane Clear Glass Wood Frame 272 9,511 0 7,316 7,316
<br /> 10C Door Wood Hollow Core & Metal Storm 40 1,325 0 340 340 �,
<br /> 13H Part R-19 + 1/2" GypsumBoard(R-0.5) 1,521 4,197 0 1,369 1,369
<br /> ', 15E Wall 5' or More Below Grade 8/12" BIk+No Insulation 350 2,801 0 0 0
<br /> � 15F Wall 5' or More Below Grade 8/12" BIk+R-5 1,035 5,619 0 0 0
<br /> 21A Basemt Floor 2' or More Below Grade 1,555 3,433 0 0 0
<br /> Subtotals for structure: 4,�49 30,738 0 10,7 i 3 i G,i 73
<br /> Active People: 9 0 2,070 2,700 4,770
<br /> Inactive People: 3 0 450 750 1,200 '
<br /> Appliances: 0 0 0 0 0
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 11,379 0 3,361 3,361
<br /> Infiltration: Winter CFM: 371.1, Summer CFM: 164.9 388 37,558 2,671 3,629 6,300
<br /> Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0
<br /> ___ _ _--- _ _
<br /> I, Sensible Gain Total: 21,213
<br /> ' Temperature Swing Multiplier: X1.00 I
<br /> Building Load Totals: 79,675 5,191 21,213 26,404
<br /> Check Figures
<br /> Total Building Supply CFM: 1035 CFM per square foot: 0.295
<br /> I Square feet of room area: 3,510 Square feet per ton: 1,489.181
<br /> Building Loads II'
<br /> ' Total heating required with outside air: 79,675 Btuh 79.675 MBH �
<br /> Total sensible gain: 21,213 Btuh 80 % �I
<br /> Total latent gain: 5,191 Btuh 20 %
<br /> Total cooling required with outside air: 26,404 Btuh 2.2 Tons (based on sensible + latent)
<br /> !, 2.357 Tons (based on 75% sensible capacity) ,
<br /> - _.__
<br /> Notes
<br /> ', Calculations are based on 7th edition of ACCA Manual J. ,
<br /> All computed results are estimates as building use and weather may vary. '
<br /> Be sure to select a unit that meets both sensible and latent loads.
<br /> . - __ . . - . - Friday,August 16, 1996 J'