'i2HVlzC'-RAs�dentia!&Light Commercial HVAC Loads =, Elite Software Devetopment,In�
<br /> Plymouth Plumbing &Heati�g ',f John Terrance Homes-2460 Sandstone Ln�
<br /> Brooklyn Center, MN 55428-1662 � Page 1J;
<br /> _ _ __ _
<br /> - -- - -- - --
<br /> -
<br /> I' ' Total Building Summary Loads �
<br /> _ _ _ -- -- - - -
<br /> ____ � _ _ ___ __ _-, _- _ I
<br /> Component Area Sen Lat Sen Total .
<br /> Description Quan Loss Gain Gain Gain !
<br /> _ _ __ _ -_ - _ __ _ __ _ _ - -
<br /> 3D Window Double Pane Low Emit Wood Frame 199 5,891 0 3,582 3,582
<br /> 11C Door Metal Polystyrene Core 42 1,619 0 367 367
<br /> 121 Wall R-19 + 1/2"Asphlt Board(R-1.3) 2216 9,995 0 2,266 2,266
<br /> 15G Wall 5'or More Below Grade 8/12" BIk+R-11 739 2,605 0 0 0
<br /> 161 Ceiling R-44 Insulation 1901 3,585 0 1,705 1,705
<br /> 21A Basemt Floor 2'or More Below Grade 1896 3,731 0 0 0
<br /> Subtotals for structure: 27,426 0 7,920 7,920
<br /> People: 6 1,380 1,800 3,180
<br /> Equipment: 300 1,200 1,500
<br /> Lighting: 0 0 0
<br /> Ductwork: 6,567 0 0 0
<br /> Infiltration: WinterCFM: 161, SummerCFM: 215 14,123 4,531 3,445 7,976
<br /> Ventilation: WinterCFM: 90, SummerCFM: 90 7,876 1,895 1,441 3,336
<br /> Sensible Gain Total: 15,806
<br /> Temperature Swing Multiplier: X 1.15
<br /> Total Building Load Totals: 55,992 8,106 18,177 26,283
<br /> -Check Fig�res � �� ����� � � � � � `�� '` �` ;:�
<br /> -� �� . ��� ��� � 'z
<br /> _� ,-...
<br /> . _�,.,ti � .,, ��r.., , ..
<br /> Total Building Supply CFM: 902 (1.7 AC/hr) ` CFM Per Square ft.: � 0.237
<br /> Square ft. of Room Area: 3,797 Square ft. Per Ton: 1,293
<br /> . -: ,
<br /> � Buildin Loads -: r,..�, x;��� �j,:�;. ,>,,.. �;�� ,� � �� __ ,�� �.
<br /> „
<br /> �> ,
<br /> . > . .; .,� ._�.. ;., �: ".,,m. , _,�'�. ,g.. . ._Q��-�' ,
<br /> ,., �. _ , �. �. ,R , .,�.,�,-
<br /> ._ ..:_.... . . „ . . .._-..............
<br /> Total Heating Required With Outside Air: 55,992 Btuh 55.992 MBH
<br /> Total Sensible Gain: 18,177 Btuh 69 %
<br /> Total Latent Gain: 8,106 Btuh 31 %
<br /> Total Cooling Required With Outside Air: 26,283 Btuh 2.19 Tons (Based On Sensible+ Latent)
<br /> 2.94 Tons(Based On 77% Sensible Capacity)
<br /> �
<br /> Notes w� .,�- '�. � __. t� y� � ,����: � ���'E ��� ��l�
<br /> � � � � v �� _
<br /> yF � ,
<br /> s �y.� ., e
<br /> Calculations are based on 7th edition of ACCA Manual J.
<br /> Afl computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads.
<br /> C:\Elite\Rhvacw\Projects\John Terrance Homes-2460 Sandstone Ln -Orono.rhv Thursday, January 15, 2004, 3:23 PM