�� e. <br /> �l ����� ���7���{� �I����d�'#�st�t�� �P'V� �'i�� <br /> CPVC Pipe Product Specifications <br /> Corrosion resistant CPVC fire sprinkler pipe, when installed in strict accordance with the manufacturer's design and instal- <br /> lation instructions, is UL and c-UL Listed by Underwriters Laboratories for use in the following: <br /> • Meets NFPA 13R and 13D standards for residential occupancies as well as NFPA 13 standards for light hazard occupancies. <br /> • Residential occupancies up to and including four stories in height as defined by NFPA 13R. <br /> • Residential occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings, NFPA 13D. <br /> • Instal(ation of private fire service mains and their appurtenances, NFPA 24. <br /> CPVC fire sprinkler pipe from Viking Plastics shail be employed in wet pipe systems only and are not listed for outdoor use. <br /> CPVC pipe must never be used in a system using compressed air or other gases. <br /> CPVC pipe from Viking Plastics also carries the follow- • Exposed sidewali sprinkler listing for exposed pipe&fittings <br /> ing enhanced listings and approvals: • 24'extended coverage sidewall sprinkler, 12"drop, 155°F <br /> • According to UL Listing sprinkler head <br /> • Can be flush at return air plenums • 18'extended coverage sidewall sprinkler, 12' drop, 165°F <br /> • Exposed system risers NFPA 13D, 13R sprinkler head <br /> • Exposed basement NFPA 13D(solid wood joist) • 16'extended coverage sidewall sprinkler, 12"drop, 175°F <br /> • Extended coverage(exposed) sprinkler head <br /> • 20'spacing on pendent in lieu of 15' • 14'standard coverage sidewall sprinkler, 12"drop,200°F <br /> • 18'spacing on sidewall in lieu of 14' sprinkler head <br /> • Use with combustible concealed sprinklers • Factory Mutual Approved* <br /> • Tyco attic sprinkler head(to protect the floor below) • Factory Mutual Approval exposed <br /> • Tyco attic sprinkler head with wet system piping • Factory Mutual Approval above drop-in ceilings <br /> (feed main and ridge installation) • Factory Mutual Approval exposed w/So�-Steel soffiting <br /> covering system <br /> New and enhanced listings and approvals are being pursued.Aiways All CPVC fire sprinkler pipe from Viking Plastics is manufactured in the <br /> check with the appropriate Listing and Approval agency for detaiis on USA.All CPVC pipe shall be packaged immediately after its manufacture <br /> current listing parameters. to prevent damage and shall be stored indoors after production,at the <br /> manufacturing site,until shipped from the factory.The pipe shail bear the <br /> CPVC pipe meets all applicable standards for pressure rated applica- logo of the listing agencies,and shall carry the National Sanitation Foun- <br /> tion as required in ANSI-NSF Standard 14 and compiies with ANSI-NSF dation(NSF)seal of approval for potabie water applications. <br /> Standard fi1 for health effects and are marked with the NSF-pw end use <br /> marking. CPVC products are intended for use in areas where the maximum ambi- <br /> ent temperature tloes not exceed 150°F(65.5'C).If the ambient tempera- <br /> All CPVC fire sprinkler pipe shall be Listed by Underwriters�aboratories ture is expected to exceed this limitation,refer to the manufacturer's DE- <br /> for wet pipe systems,and shail carry a rated working pressure of 175 psi SIGN AND INSTALLATION GUIDE for additional information on methods <br /> �150°F(12 bar @ 65.5'C)."The FM Approval is limited to use in wet to reduce the pipe exposure temperatures.CPVC pipe is not intended to <br /> pipe fire protection sprinkier systems for light hazard occupancies in both be installed in outdoor appiications. CPVC pipe is intended to be used in <br /> concealed and exposed appiications with certain restrictions. wet pipe systems only and have not been investigated for use in dry pipe <br /> systems.Special installation and design criteria relative to pipe hanger <br /> Piping must always be installed in strict accordance to the manufacturer's spacings,piping and sprinkler restraint,sprinkler temperature rating, <br /> DESIGN AND INSTALLATION GUIDE,including product storage and piping locations,testing procedures and friction loss characteristics are <br /> handling,joining methods,supporting and bracing,expansion and con- specified in the manufacturer's installation instructions provided with the <br /> traction allowance and testing,eta National Fire Protection Association pipe.The manufacturer's installation instructions shc dd be reviewed and <br /> (NFPA)Standards 13, 13D,and 13R must be referenced for design and the Authority Having Jurisdiction consulted before installation. <br /> instailation requirements in conjunction with the installation instructions. <br /> � <br /> Trusted above all"" ��������� <br />