<br /> Rhvac-Residential 8 Light Commercial HVAC Loads Elite Software Development,Inc �
<br /> i ' Pronto Heating and AC- _ - . _ _ _ - .--. � - - - - - - - _ - -Church Residence�
<br /> Eden Prairie,MN 55344 _ Pa e 3
<br /> � otal Building_Summary Loads �
<br /> _ _ _ _ - - - - - _� i
<br /> � De cP�tiont _-- - _ - - - -- - -Quan Loss _ _ Ga n - Ga n -- Ga nl I i
<br /> ! 1 D-cv-o: G lazing-Dou b le pane, opera b le win dow, c lear, 1 2 3 8 6 0,6 8 7 0 3 5,1 3 2 3 5,1 3 2 �
<br /> vinyl frame, outdoor insect screen with 50%
<br /> coverage, light color closed blinds with 100%
<br /> coverage, u-value 0.57, SHGC 0.56
<br /> , 11 N: Door-Metal - Polystyrene Core 60 1,806 0 714 714
<br /> 12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 4599.9 26,902 0 7,946 7,946
<br /> cavity, no board insulation, siding finish, wood studs i
<br /> 15611-Om-4: Wall-Basement, , framing with R-11 sill to 2050 17,771 0 2,611 2,611
<br /> floor in 2 x 4 cavity, core, no board insulation, plus I
<br /> interior finish, metal studs, 4'floor depth
<br /> 15B0-6sf-10: Wall-Basement, , R-6 board insulation to 1852.5 14,655 0 2,332 2,332
<br /> floor, no interior finish, 10'floor depth
<br /> 16CR-38: Roof/Ceiling-Under Attic with Insulation on Attic 3826 8,555 0 4,775 4,775
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic with Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or �
<br /> Membrane, R-38 insulation
<br /> 20P-21: Floor-Over open crawl space or garage, Passive, 24 97 0 20 20
<br /> R-21 blanket insulation, any cover
<br /> 21A-20: Floor-Basement, Concrete slab, any thickness, 2 4537 10,534 0 0 0
<br /> or more feet below grade, no insulation below floor, I
<br /> any floor cover, shortest side of floor slab is 20'wide I
<br /> Subtotals for structure: 141,007 0 53,530 53,530 I
<br /> People: 18 3,960 5,400 9,360 I
<br /> Equipment: 900 1,200 2,100 �
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 298, Summer CFM: 148 27,313 2,953 3,627 6,580
<br /> Ventilation: Winter CFM: 200, Summer CFM: 250 18,357 4,997 6,137 11,134
<br /> Exhaust: Winter CFM: 200, Summer CFM: 200 i
<br /> AED Excursion: 0 0 6,802 6,802
<br /> ; Total Building Load Totals: 186,677 12,810 76,696 89,506
<br /> I [Tot I Bui dUneSSu I CFM� 3,306 CFM Per S uare ft.: 0.294 I
<br /> 9 PP Y q
<br /> I Square ft. of Room Area: 11,233 Square ft. Per Ton: 1,506
<br /> Volume (ft3) of Cond. Space: 114,749
<br /> Buildin Loads
<br /> Total Heating Required Including Ventilation Air: 186,677 Btuh 186.677 MBH
<br /> � Total Sensible Gain: 76,696 Btuh 86 %
<br /> Total Latent Gain: 12,810 Btuh 14 °/a
<br /> Total Cooling Required Including Ventilation Air: 89,506 Btuh 7.46 Tons (Based On Sensible + Latent) I
<br /> -_- _ _ __- -_.-__ _ -_---
<br /> Notes
<br /> �
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\ ...\Stonewood-Church.rh9 Monday, November 04, 2013, 3:22 PM