Norw odRMN 55368�'L ght Commercial HVAC Loads � Elite S�0 B h LanepO o age 6,
<br /> Total Building Summary Loads
<br /> _ _ __ __ _. __ _ _ .
<br /> __ _ __ __ _ ___--- —_ _ _ _ __ _ -- — __ __ - _ -
<br /> Component Area Sen Lat Sen Total
<br /> Description Quan Loss Gain Gain Gain
<br /> 1D-rm-o: Glazing-Double pane, operable window, 413.6 29,155 0 10,003 10,003
<br /> reflective, metal frame no break, u-value 0.87, SHGC
<br /> 0.27
<br /> 11 Q: Door-Metal - Polyurethane Core With Storm 42 578 0 172 172
<br /> 12C-Osw: Wall-Frame, R-13 insulation in 2 x 4 stud 1121.6 8,266 0 1,991 1,991
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 12F-Osw: Wall-Frame, R-21 insulation in 2 x 6 stud 877.5 4,620 0 758 758
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 166-0: Roof/Ceiling-Under Attic with Insulation on Attic 444 14,674 0 8,695 8,695
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-0 insulation
<br /> 16B-44: Roof/Ceiling-Under Attic with tnsulation on Attic 443.6 791 0 468 468
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-44 insulation
<br /> 16A-44: Roof/Ceiling-Under Attic with Insulation on Attic 312 556 0 467 467
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Unvented Attic, No Radiant Barrier,Any
<br /> Roofing Material, Any Roof Color, R-44 insulation
<br /> Subtotals for structure: 58,640 0 22,554 22,554
<br /> People: 0 0 0 0
<br /> Equipment: 0 0 0
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 132, Summer CFM: 68 11,444 1,052 941 1,993
<br /> Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> Total Building Load Totals: 70,084 1,052 23,495 24,547
<br /> - _ - --- -- ----_;
<br /> Check Figures
<br /> --- - — --_ __-- ---
<br /> _._ _. _. ._ --- ---- — — __ ._ _._ — ---- �
<br /> Total Building Supply CFM: 1,101 CFM Per Square ft.: 0.467
<br /> Square ft. of Room Area: 2,356 Square ft. Per Ton: 1,152
<br /> Volume(ft) of Cond. Space: 19,374
<br /> - - - -- .__
<br /> Building Loads - . - - --- - --
<br /> _ __ _--- - ___ _ _-- -----—. ..----
<br /> Total Heating Required Including Ventilation Air: 70,084 Btuh 70.084 MBH
<br /> Total Sensible Gain: 23,495 Btuh 96 %
<br /> Total Latent Gain: 1,052 Btuh 4 %
<br /> Total Cooling Required Including Ventilation Air: 24,547 Btuh 2.05 Tons (Based On Sensible+ Latent)
<br /> Notes ._ __ _- --- ----- _--------
<br /> __ _- _ _ _ ___ _ __ _ _ ._ _ _ __ ____;
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\UserslStephanie\Documents\Elite Software\Rhvac 9 Projects\Lisle-Orono.rh9 Wednesday,April 8, 2015, 7:10 PM