Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
<br /> Ferguson Enterprises[Plymout � Bill's Heating-770 Brown
<br /> ' Plymouth,MN 55441 _ -- _ __ _- --._ Paqe 4
<br /> -- _ _--- - -
<br /> Total Building Summary Loads ____ __ _
<br /> -- _ _ _ _- -_
<br /> _- - --
<br /> Component Area Sen Lat Sen Total
<br /> ,Description � „�__ Quan Loss_ _�Gain __Gain Gain
<br /> 1D-cv-d: Glazing-Double pane, sliding glass door, clear, 180 8,412 0 6,024 6,024
<br /> , vinyl frame, u-value 0.57, SHGC 0.56
<br /> 1D-cv-o: Glazing-Double pane, operable window, clear, 484.1 22,627 0 19,124 19,124
<br /> vinyl frame, u-value 0.57, SHGC 0.56
<br /> 11 K: Door-Metal - Fiberglass Core With Storm 63 1,860 0 567 567
<br /> 12F-Osw: Wall-Frame, R-21 insulation in 2 x 6 stud 1945.9 10,372 0 1,808 1,808
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 15A-20sffc-10: Wall-Basement, concrete block wall, R-20 891 1,900 0 0 0
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 10'floor depth
<br /> 16B-50: Roof/Ceiling-Under Attic with Insulation on Attic 1850 3,034 0 1,813 1,813
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark �
<br /> , Asphalt Shingles or Dark Metal, Tar and Gravel or I
<br /> Membrane, R-50 insulation
<br /> ', 22A-pm: Floor-Slab on grade, No edge insulation, no 175 16,933 0 0 0
<br /> I insulation below floor, any floor cover, passive, heavy il
<br /> � dry or light wet soil
<br /> I' Subtotals for structure: 65,138 0 29,336 29,336 I�'�
<br /> People: 14 2,800 3,220 6,020 I
<br /> Equipment: 0 0 0 i
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: WinterCFM: 241, SummerCFM: 125 21,129 2,763 1,866 4,629
<br /> Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> AED Excursion: 0 0 2,935 2,935_
<br /> Total Building Load Totals: 86,267 5,563 37,357 42,920
<br /> � Check Figures �
<br /> Total Building Supply CFM: 1,750 CFM Per Square ft.: 0.473
<br /> Square ft. of Room Area: 3,700 Square ft. Per Ton: 1,034
<br /> Volume (ft') of Cond. Space: 33,300 ;
<br /> � Building Loads -- ___ _.-------- --- ��
<br /> Total Fieating Required Including Ventilation Air: 86,267 Btuh 86.267 MBH ,
<br /> Total Sensible Gain: 37,357 Btuh 87 % i
<br /> Total Latent Gain: 5,563 Btuh 13 %
<br /> I Total Cooling Required Including Ventilation Air: 42,920 Btuh 3.58 Tons (Based On Sensible + Latent)
<br /> - --- - _ _ ___. __
<br /> --- -------- -
<br /> Notes __
<br /> ----- --- - --_ _.. __
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> I Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> i your design conditions.
<br /> C:\UsersWAM4100\Desktop\Heat Load Calc\Bill's Heating-770 Brown.rh9 Monday, January 25, 2016, 7:29 AM