Laserfiche WebLink
Adtek Software Co Kyle Hunt and partners <br /> 105 S Main St-Toluca, ill 61369 Lieberman <br /> 815-452-2345 -sales@adteksoft.com Orono , Mn <br /> Sales Consultant: <br /> Job#: <br /> Date: 09I12/2013 <br /> Sysfem / (Average Load Procedure) <br /> Design Conditions <br /> Location: Minneapolis/St Paul AP, Minnesota Elevation: 834 ft Daily Range: Medium <br /> Input Data: Outdoor Dry Bulb Indoor Dry Bulb Latitude: 44° N Design Grains: 24 <br /> Summer: 88 75 Heated Area 5170 Sq.Ft. <br /> Winter: -11 70 Cooled Area 5170 Sq.Ft. <br /> Heat/�oss Summary (July Heat Load Calculations) <br /> Sensible Latent <br /> Loss Gain Gain <br /> Walls 13286 1470 0 <br /> Windows 20349 20797 0 <br /> Doors 1770 566 0 <br /> Ceilings 3524 1305 0 <br /> Skylights 0 0 0 <br /> Floors 3924 d 0 <br /> Room Internal �oads 0 Q 0 <br /> Blower Load 1707 0 <br /> Hot Water Piping Load 0 0 0 <br /> Winter Humidification Load 0 0 0 <br /> Infiltration 33666 5299 6047 '" � __���� <br /> ;�� , <br /> Ventilation 32745 5255 5998 � -^��-'�=� <br /> Duct Loss/Gain EHLF=O ESGF=O 0 0 0 <br /> AED Excursion n/a 0 n/a <br /> Subtotal 109264 36399 12045 <br /> Total Heating 109264 Btuh 33 kw of electric heat <br /> Total Cooling 48444 Btuh 215 Linear ft. of Hydronic Baseboard <br /> *Calculations are based on the ACCA Manual J 8th edition. All computed calculations are estimates based on <br /> building use,weather data, and inputted values such as R-Values,window types, duct loss, etc. Equipment <br /> selection should meet both the latent and sensible gain as well as building heat loss. <br /> Adtek AccuLoad Repo�t Version 1.4.1 Page 1 <br />