'� �Rhvac-Residential8 Light Commercial HVAC Loads Elife Soflware Developme�t,Inc.! '
<br /> 'Sabre Plumbing 8�Heating � 2470 Carmen St,James Residence,
<br /> ' Plymouth,MN 55447 Page 6.
<br /> _ _
<br /> �� ; Total Building Summary Loads
<br /> I I Component Area Sen Lat Sen Totai;
<br /> � Description Quan Loss Gain Gain Gain;
<br /> New Material: Glazing-Low E Builder Grade: Glazing- 959.8 27,243 0 28,330 28,330 '.
<br /> Builder Grade Low E Windows&Sliding Door.33 U
<br /> value.33 SHGC, u-value 0.33, SHGC 0.33
<br /> 11J: Ooor-Metal-Fiberglass Core 48 2,476 0 748 748 i
<br /> 12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 5208.2 30,458 0 6,162 6,162 ��
<br /> cavity, no board insulation, siding finish, wood studs �
<br /> 16B-44: Roof/Ceiling-Under Attic with Insulation on Attic 3507.5 6,636 0 3,858 3,858 �
<br /> �,, Ftoor(also use for Knee Walls and Pa�tition
<br /> ' Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or I
<br /> Membrane, R-44 insulation i
<br /> � 218-28-c: Floor-Basement, Concrete slab, any thickness, 2865.9 3,697 0 0 0 i
<br /> i 2 or more feet below grade, R-3 or higher insulation ,
<br /> � installed below floor, carpet covering, shortest side of
<br /> � floor slab is 28'wide
<br /> � 20P-38: Floor-Over open crawl space or garage, Passive, 1066.6 2,752 0 320 320 ,
<br /> R-38 blanket insulation, any cover ,
<br /> Subtotals for structure: 73,262 0 39,418 39,418 ,
<br /> People: 4 800 920 1,720 '
<br /> � Equipment: 0 0 0
<br /> iLighting: 0 0 0 �
<br /> , Ductwork: 0 0 0 0
<br /> � Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0 �
<br /> � Ventilation: Winter CFM: 110, Summer CFM: 110 10,096 2,316 1,761 4,077 �
<br /> AED Excursion: 0 0 5,475 5,475 �
<br /> j Total Building Load Totals: 83,358 3,116 47,574 50,690
<br /> ___ -- _
<br /> 'Check Figures _
<br /> ___
<br /> Total Building Supply CFM: 2,146 CFM Per Square ft.: 0.337
<br /> Square ft. of Room Area: 6,374 Square ft. Per Ton: 1,509 ,
<br /> Volume(ft') of Cond. Space: 62,667 '
<br /> _ __ __
<br /> Building Loads
<br /> -- - _ _ __ _ _: ,
<br /> ' Total Heating Required Including Ventilation Air: 83,358 Btuh 83.358 MBH
<br /> j Total Sensible Gain: 47,574 Btuh 94 %
<br /> ' Total Latent Gain: 3,116 Btuh 6 %
<br /> , Total Cooling Required Including Ventilation Air: 50,690 Btuh 4.22 Tons (Based On Sensible+ Latent)
<br /> � ; Notes _ _ ___ _ _
<br /> _ _ �
<br /> ' Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. �
<br /> All computed results are estimates as building use and weather may vary. '
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufactu�er's performance data at �
<br /> ' your design conditions.
<br /> I
<br /> i
<br /> S:IJARNES RESIDENCE Heat Calc.rh9 Tuesday, December 02, 2014, 8:53 AM