<br /> PLYMOUTH PLUMBING & HEATING PROJECT: BOHL RESIDENCE
<br /> 6909 WINNETKA AVENUE NORTH CLIENT: PILLAR HOMES
<br /> MINNEAPOLIS, MN 55428 DATE: NOVEMBER 30, 1999
<br /> RESIDENTIAL/LIGHT COMMERCIAL HVAC LOADS DESIGNER: Terry Vereide
<br /> CLIENT INFORMATION:
<br /> NAME: PILLAR HOMES
<br /> ADDRESS : �;�� '3;zyr �� �
<br /> CITY, STATE:
<br /> TOTAL BUILDING LOADS :
<br /> ------------------------------------------------------------------------------
<br /> BLDG. LOAD AREA SEN. LAT. + SEN. = TOTAL
<br /> DESCRIPTIONS QUAN LOSS GAIN GAIN GAIN
<br /> ------------------------------------------------------------------------------
<br /> 4-C WIND. DBL PN&STM CLR GLS METL F 351 15, 822 0 14, 870 14, 870
<br /> 9-G FRENCH DOOR DBL CLR GLS WOOD FR 168 8, 069 0 7, 610 7, 610
<br /> 12-I WALL R-19 +l/2"ASPHLT BRD (R-1 . 3) 3 , 422 17, 316 0 3, 877 3 , 877
<br /> 15-G WALL >5 'BELOW GRD 8" BLK+R-11 795 3 , 145 0 0 0
<br /> 11-C DOOR METAL POLYSTYRENE CORE 84 3, 632 0 813 813
<br /> 16-H CEILING R-38 INSULATION 2, 764 6, 611 0 2, 946 2, 946
<br /> 19-G FLOOR/ENCL CRAWL CARPET + R-11 2, 688 8, 779 0 0 0
<br /> 21-A BASEMT FLOOR 2 'OR> BELOW GRADE 2, 688 5, 935 0 0 0
<br /> ------------------------------------------------------------------------------
<br /> SUBTOTALS FOR STRUCTURE: 12, 960 69, 309 0 30, 116 30, 116
<br /> PEOPLE 7 0 1, 610 2, 100 3, 710
<br /> APPLIANCES 0 0 1, 200 0 1, 200
<br /> DUCTWORK 0 0 0 0 0
<br /> INFILTRATION W.CFM: 286 .2 S .CFM: 190 . 8 0 28, 968 4, 282 3, 568 7, 850
<br /> VENTILATION W.CFM: 90 . 0 S .CFM: 90 . 0 0 9, 108 2, 020 1, 683 3, 703
<br /> ------------------------------------------------------------------------------
<br /> SENSIBLE GAIN TOTAL 37, 467
<br /> TEMP. SWING MULTIPLIER X 1 . 00
<br /> BUILDING LOAD TOTALS 107, 384 9, 112 37, 467 46, 579
<br /> ------------------------------------------------------------------------------
<br /> SUPPLY CFM AT 20 DEG DT: 1, 627 CFM PER SQUARE FOOT: 0 .239
<br /> SQUARE FT. OF ROOM AREA: 6, 820 SQUARE FOOT PER TON: 1, 757 . 015
<br /> TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 107 .384 MBH
<br /> TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 3 . 882 TONS
<br /> CALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J.
<br /> ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY.
<br /> BE SURE TO SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS .