<br /> PLYMOUTH P�+UMBING & HEATING PROJECT: HAHN RESIDENCE
<br /> 6909 WINNETKA AVENUE NORTH CLIENT: MICHAEL HAYES
<br /> MINNEAPOLIS, MN 55428 DATE: MARCHI7, 2000
<br /> RESIDENTIAL/LIGHT COMMERCIAL HVAC LOADS DESIGNER: Terry Vereide
<br /> CLIENT INFORMATION:
<br /> NAME: MICHAEL HAYES
<br /> ADDRESS : ARCHETYPE BUILDERS
<br /> CITY, STATE:
<br /> TOTAL BUILDING LOADS :
<br /> ------------------------------------------------------------------------------
<br /> BLDG. LOAD AREA SEN. LAT. + SEN. = TOTAL
<br /> DESCRIPTIONS QUAN LOSS GAIN GAIN GAIN
<br /> ------------------------------------------------------------------------------
<br /> 4-C WIND. DBL PN&STM CLR GLS METL F 1, 264 56, 982 0 51, 608 51, 608
<br /> 9-G FRENCH DOOR DBL CLR GLS WOOD FR 292 14, 023 0 9, 744 9, 744
<br /> 12-I WALL R-19 +1/2"ASPHLT BRD (R-1 . 3) 3, 243 16, 409 0 3, 676 3 , 676
<br /> 15-G WALL >5 'BELOW GRD 8" BLK+R-11 908 3, 592 0 0 0
<br /> 11-C DOOR METAL POLYSTYRENE CORE 65 2, 811 0 629 629
<br /> 16-H CEILING R-38 INSULATION 2 , 797 6, 691 0 2, 982 2 , 982
<br /> 20-J FLOOR/OPEN CR.AWL CARPET + R-30 1, 080 3, 478 0 454 454
<br /> 21-A BASEMT FLOOR 2 'OR> BELOW GRADE 2, 696 5, 953 0 0 0
<br /> ------------------------------------------------------------------------------
<br /> SUBTOTALS FOR STRUCTURE: 12 , 345 109, 939 0 69, 093 69, 093
<br /> PEOPLE 9 0 2, 070 2, 700 4, 770
<br /> APPLIANCES 0 0 0 2, 400 2, 400
<br /> DUCTWORK 0 0 0 0 0
<br /> INFILTRATION W.CFM: 344 .6 S .CFM: 229 . 7 0 34, 872 5, 155 4, 296 9,451
<br /> VENTILATION W.CFM: 90 . 0 S .CFM: 90 . 0 Q 9, 108 2, 020 1, 683 3, 703
<br /> ------------------------------------------------------------------------------
<br /> SENSIBLE GAIN TOTAL 80, 172
<br /> TEMP. SWING MULTIPLIER X 1 . 00
<br /> BUILDING LOAD TOTALS 153 , 920 9, 245 80, 172 89, 417
<br /> ------------------------------------------------------------------------------
<br /> SUPPLY CFM AT 20 DEG DT: 3 , 568 CFM PER SQUARE FOOT: 0 .450
<br /> SQUARE FT. OF ROOM AREA: 7, 928 SQUARE FOOT PER TON: 1, 063 . 959
<br /> TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 153 . 920 MBH
<br /> TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 7 .451 TONS
<br /> CALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J.
<br /> ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY.
<br /> BE SUR.E TO SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS .