Laserfiche WebLink
TO: Thomas Jacobs, Building Inspector <br />Jeanne Mabusth, Zoning Administrator <br />FROM: Michael Gaffron, On -Site Systems Manager <br />DATE: October 14, 1980 <br />SUBJECT: Addition - 2620 Fox Street, buehrer <br />I reviewed and inspected this existing system today. By probing <br />and direct measurement, I found that the first septic tank is <br />approximately 1110" from the existing house. The Buehrers propose <br />a 12' extension to the west of existing house. Since the footings <br />for the two story addition would fall directly over the tank cover, <br />it will be necessary to remove the tank and replace it with a new <br />precast 1,000 gallon tank (to meet code for first tank to one side <br />(see sketch). <br />The applicant should be warned that the existing drainfield and <br />second tank will be in close proximity to the construction and must <br />not be disturbed i.e. no driving over it, piling fill, caterpillars, <br />etc. Also, septic contractor should repair cKiGting second tank <br />as necessary and add stacks to it. <br />