Laserfiche WebLink
I <br />TO: <br />PROM: <br />DATE:' <br />SUBJECT: <br />Jeanne A. Mabusth, Zoning Administrator <br />Michael P. Gaffron, Septic System Inspector <br />September 16, 1981 <br />#642 Lachlan Reed, 1500 Brackett's Point Road <br />Subdivision <br />X have reviewed this subdivision and wish to make the following <br />comments: <br />Lot 1 has an acceptable percolation rate and depth to saturated <br />zone for a standard system. When construction plans are made, <br />care should be taken to keep the system above approximately <br />the 936 contour line. <br />Lot 2 has adequate area for a future septic system should the <br />existing system fail. <br />Lot 3 - The guest house cottage should have a new septic system <br />installed as long as continued use is desired. It may be <br />necessary to install new tanks, and a pump appears to be required. <br />Assuming a two bedroom house, the minimum design size of drainfield <br />%#o\ :d be 250 square feet. Since this building receives inter­ <br />mittent usage, the Orono Code requirement of 600 square feet <br />for each dwelling unit can be waived. <br />• - <br />A: ^ <br />n