k i <br /> Resolution <br /> SP TESTING INC. Exhibit B <br /> Steven B.Schlrmers—951 Katydid Lane NE—St.Midas!,MN 55376 <br /> Cert.No 627—State License 9394—Phone 763-497-3566—Fax 763-497-5011 <br /> www.satestine.wastewaterecomcast.ne%— schlrmerswastewater.com <br /> February 11,2015 <br /> Chris Perrry <br /> 1125 Hunter Dr. <br /> Orono, MN <br /> This site has an existing on-site sewage treatment system which has a <br /> Multi-Flo Wastewater Treatment System. <br /> A restroom Is proposed in the existing barn,garage. This will require <br /> A 1000 gallon pumping tank with 2 maintenance holes,one for the <br /> trash trap&one for a pump vault which will pump 50ga1/cycle to the <br /> existing pumping chamber#1 entering at the riser. The supply line will <br /> need to be a directional bore& insulated through the driveway at a <br /> minimum. A'/4"diameter pipe is available which is all insulated per <br /> Elmer J.Peterson Co. The 4"supply line from the barn,top of the tank <br /> &2'down the sides must be insulated. The ground at pump tank#1 is <br /> elev.96.6 &the top of the tank at elev.94.2 <br /> All neighboring wells are located greater than 100'away from the <br /> proposed system. <br /> The pump will be 1/2hp with 33'of head at 25 gal/min. The supply line <br /> will 185'long&be 1-114"diameter, (7.8 gal/100'x 185'a 14'of drain <br /> back). The pump will cycle 50 gal & 14 gallons drain back pumping 64 <br /> gal/cycle. <br /> Steven B. Schinners <br /> FEB 12 2015 <br /> 3718 <br />