Model F1 Res 30 LL, 49 LL & 58 LL CCP Pendent <br />(Concealed) Specifications <br />Sprinklers shall be [cULus Listed] [WaterMark Certified <br />WMCS] low flow residential concealed sprinklers engi- <br />neered to provide a minimum design density of 0.05 gpm/ <br />ft2 over the listed coverage area. Listed flows as speci- <br />fied by the manufacturer’s technical data sheets are to be <br />used. Residential sprinklers shall be installed in confor- <br />mance with the manufacturer’s installation guidelines and <br />the applicable installation standard. Sprinkler frame and <br />deflector shall be of bronze frame construction having a ½” <br />NPT thread. Water seal assembly shall consist of a PTFE- <br />coated Belleville spring washer with top-loaded extruded <br />or cold head cup with 3 mm glass bulb containing no plas- <br />tic parts, and having a temperature rating of 155°F (68°C). <br />Cover plate assembly shall consist of a brass cover plate <br />and copper alloy retainer flange. Method of attaching the <br />cover plate to the sprinkler cup shall be a push-on and <br />thread-off design allowing a ½” cover plate adjustment. <br />Cover plate temperature rating shall be 135°F (57°C). A <br />plastic protective cap shall be provided and factory in- <br />stalled inside the sprinkler cup to protect the sprinkler from <br />damage, which could occur during construction before the <br />cover plate is installed. Standard cover plate finish: [White] <br />[Custom Color– specify]. ]. Concealed pendent sprinklers <br />shall be Reliable Model F1 Res 30 LL, 49 LL & 58 LL CCP, <br />SIN RA3311, RA3316 & RA3313 (Bulletin 033). <br />Model F1 Res 44 LL Horizontal Sidewall <br />Residential Sprinkler Specifications <br />Sprinklers shall be [cULus Listed] [WaterMark Certified <br />WMCS] low flow residential horizontal sidewall sprinklers <br />engineered to provide a minimum design density of 0.05 <br />gpm/ft2 over the listed coverage area. Listed flows as <br />specified by the manufacturer’s technical data sheets are to <br />be used. Residential sprinklers shall be installed in confor- <br />mance with the manufacturer’s installation guidelines and <br />the applicable installation standard. Sprinkler frame and <br />deflector shall be of bronze frame construction having a ½” <br />NPT thread. Water seal assembly shall consist of a PTFE- <br />coated Belleville spring washer with top-loaded extruded <br />or cold head cup with 3 mm glass bulb containing no plas- <br />tic parts, and having a temperature rating of [155°F (68°C)] <br />[175°F (79°C)]. Sprinklers shall have a nominal K-factor <br />of 4.4 (62.8). Standard finish: [Bronze] [Chrome-plated] <br />[White Polyester] [Special finish– specify]. Residential hori- <br />zontal sidewall sprinklers shall be Reliable Model F1 Res <br />44 LL, SIN RA3331 (Bulletin 033). <br />Model F1 Res 44 LL Recessed <br />Horizontal Sidewall Sprinkler Specifications <br />Use description for the Model F1 Res 44 horizontal side- <br />wall sprinkler with the following modifications: Replace <br />“horizontal sidewall sprinkler” with “recessed horizontal <br />sprinkler.” Add: Recessed escutcheon assembly shall be <br />a steel, two-piece escutcheon with ½” adjustment (Model <br />F2). Standard finish shall be [brass][bright chrome] [white <br />painted] [Special finish– specify]. Residential recessed <br />horizontal sidewall sprinklers shall be Reliable Model F1 <br />Res 44 LL/F2, SIN RA3331 (Bulletin 033). <br />Standard Finishes <br />Sprinkler F1, F2, FP <br />Escutcheons Cover Plates <br />Bronze <br />Chrome Plated <br />White and Black Polyester <br />Coated <br />Brass <br />Bright Chrome Plated <br />White Painted <br />White Painted <br />Chrome <br />Special Application Finishes <br />Sprinkler F1, F2, <br />Escutcheons Cover Plates <br />Bright Brass <br />Black Plated <br />Black Paint <br />Off White <br />Satin Chrome <br />Bright Brass <br /> Black Plated <br />Black Paint <br />Off White <br />Satin Chrome <br />Bright Brass <br />Black Plated <br />Black Paint <br />Off White <br />Satin Chrome <br />(1) Other finishes and colors are available on special order. <br /> Consult factory for details. <br />Note: Paint or any other coating applied over the factory finish will void <br />all approvals and warranties. <br />Ordering Information <br />Specify: <br />1. Sprinkler Model <br />2. Sprinkler Type <br />3. Temperature Rating <br />4. Sprinkler Finish <br />5. Escutcheon Finish <br />6. Cover Plate Finish <br />Reliable Automatic Sprinkler Co., Inc. <br />(800) 431-1588 Sales Offices <br />(800) 848-6051 Sales Fax <br />(914) 829-2042 Corporate Offices <br />www.reliablesprinkler.com Internet Address <br />Manufactured by <br />Recycled <br />Paper <br />Revision lines indicate updated or new data. <br />EG. Printed in U.S.A. 06/20 P/N 9999970411 <br />The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory <br />Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. <br />Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.