Laserfiche WebLink
FIRE SUPPRESSION SERVICES Page 1 <br />ORONO COMMONS Date 092908 <br /> <br /> HYDRAULIC DESIGN INFORMATION SHEET <br /> <br />Name - ORONO COMMONS Date - 5-25-23 <br />Location - FIRST FLOOR DA-1 <br />Building - 2430-2440 NORTH BLOSSOM CIRCLE System No. - <br />Contractor - FIRE SUPPRESSION SERVICES Contract No. - <br />Calculated By - J GANTER Drawing No. - FP-1 <br />Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9' <br />OCCUPANCY - RESIDENTIAL <br /> <br /> <br />S Type of Calculation: (34)NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D <br />Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4 ( ) <br />S ( )Other <br />T ( )Specific Ruling Made by Date <br />E <br />M Listed Flow at Start Point - 17 Gpm System Type <br /> Listed Pres. at Start Point - 12 Psi (X) Wet ( ) Dry <br />D MAXIMUM LISTED SPACING 18 x 18 ( ) Deluge ( ) PreAction <br />E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle <br />S Additional Flow Added - Gpm Make RELIABLE Model RES 49 <br />I Elevation at Highest Outlet - 10.25Feet Size 1/2 K-Factor 4.9 <br />G Note: Temperature Rating 155 <br />N <br /> <br /> <br />Calculation Gpm Required 34.8 Psi Required 34.3 At P0C <br />Summary C-Factor Used: Overhead 150 Underground 150 <br /> <br /> <br />W Water Flow Test: Pump Data: Tank or Reservoir: <br />A Date of Test - 12-1-21 Rated Cap. Cap. <br />T Time of Test - 11:00 AM @ Psi Elev. <br />E Static (Psi) - 61 Elev. <br />R Residual (Psi) - - Other Well <br /> Flow (Gpm) - -- Proof Flow Gpm <br />S Elevation - 2 <br />P Location: WILLOW DRIVE & KELLEY PKWY <br />P <br />L Source of Information: STATIC PRESSURE GAUGED AT SITE <br />Y <br /> <br /> <br /> <br />Computer Programs by Hydratec Inc. Route 111 W indham N.H. USA 03087