Laserfiche WebLink
AER13SEAL <br />Brackets Point Project, JK and Sons <br />1400 Brackets Point RD <br />Orono, MN 55391 <br />DATE: <br />10/18/2021 <br />Overall Sealing <br />BEFORE SERVICE <br />50.6 CFM of Leakage, equivalent to a <br />9.6 Square Inch Hole or <br />2.5% of the system capacity of 2000.0 CFM <br />AFTER SERVICE <br />6.5 CFM of Leakage, equivalent to a <br />1.2 Square Inch Hole or <br />0.33% of system capacity <br />This corresponds to a <br />87% Reduction <br />in Duct Leakage <br />NOTE: Duct leakage results are calculated in Cubic <br />Feet per Minute (CFM) measured at a STANDARD <br />OPERATING PRESSURE of 25 Pa. <br />rsa��r �r�r-i is�rr4 a. a. � Zv�ti asr <br />SO/�YC� y+Gsr! �GriY/OYI ��rY�. <br />DUCT <br />SEALING REPORT <br />AEROSEAL CASE ID: 5261 <br />SYSTEM DESCRIPTION: HP101B <br />SEAL DESCRIPTION: Return <br />HARDWARE: HomeSeal Connect <br />TECHNICIAN: Kevin C <br />6( <br />C40 <br />L <br />LI) <br />�3 <br />0 <br />03 <br />LL <br />20 <br />04 <br />0 <br />1 2 3 4 <br />Sealing Time in Minutes <br />Select Mechanical Services <br />6219 Cambridge Street <br />St. Louis Park, MN 55416 <br />Phone: 952-926-4488 <br />5 6 <br />Aeroseal process uses DuctSeal sealant that is certified to meet requirements listed in UL 1381 standard -"Outline of investigation for Aerosol Duct Sealant" <br />Please provide Aeroseal feedback at http://bit.ly/2021aeroseal and reference code MKPNRJTY. <br />SmartSeal 4.3.3.23 (5261-22-76-148) 1 of 1 <br />