Laserfiche WebLink
Specification for WSHP SmartSource ALL <br />T. Intelligent Reset: (Low pressure and Low temperature in heating only). The "Fault Retry' feature helps to <br />minimize nuisance trips of automatic lockouts caused by low-pressure or low temperature faults. This feature <br />automatically clears these faults the first two times they occur within a 24-hour period and triggers an automatic <br />lockout on the 3rd fault. The retry count is reset to zero every 24 hours. The fault retry feature does not apply to a <br />high pressure fault — which causes an immediate lockout and requires a manual reset, or condensate overflow or <br />brownout faults—which are self -clearing. <br />U. Microtech III Unit Controller and 1/0 Expansion Board Fault and Status LEDs: Separate remote LED boards will <br />provide visual feedback for both control modules. <br />1. Room Sensor Status LED: A SVDC signal and shall operate as follows: <br />Status LED <br />Slade <br />On continually <br />Occupied, Occupied Load Shed <br />On 0.5 sec, Off 5.5 sec <br />Unoccupied <br />On 5.5 sec. Off 0.5 sec <br />Tenant Override. Override Load Shed <br />On 0.1 sec, Off 0.1 sec <br />Al= Condition (Condensate Overilow- <br />Ermvrout, Compressor Fault) <br />V. Auxiliary Relay Output: A 24VAC signal which is turned on when the unit is in alarm mode. <br />Job Number: LL2OFE Page Prepared Date: 10/8/2020 <br />Job Name: Brackets Point House 34 of 35 www.DaikinApplied.com <br />