Laserfiche WebLink
From: negan@ci.orono.mn.us <br />Sent: 07/01/2022 - 11:43 AM <br />To: jason@selectmechanical.com,negan@ci.orono.mn.us <br />CC: <br />Subject: Inspection Report Email - Failed <br />Inspection Report <br />1400 BRACKETTS POINT RD <br />Permit Number: M20-000009 <br />Site Address: 1400 BRACKETTS POINT RD, WAYZATA, MN 55391 <br />Property Owner: BRACKETT POINT PROPERTY LLC <br />Description: New home HVAC system <br />Inspection Date: 07/01/2022 <br />Inspection Type: Mechanical - Final <br />Inspection Results: Inspection Failed: Reinspect <br />CITY OF ORONO <br />2750 KELLEY PARKWAY <br />ORONO, MN 55356 <br />PH: (952) 249-4600 <br />FAX: (952) 249-4616 <br />Inspection Status: Re -inspection Required <br />1. All bath fans must be tested <br />2. All manifold penetrations must be fire blocked <br />3. Ductwork on both sides of bridge must be fire blocked <br />4. All access panels are required to be gasketed <br />Inspection Status: Review Comment <br />1. Energy seal report/Blower door/energy certificates/Balance report are required at final inspection. Duct static pressure must be below 3. <br />2. Provide truss verification that trusses in boiler room are able to hold additional weight of hanging pipes. <br />3. Did gas leak test on all gas connections - compliant. <br />Sincerely, <br />1P�u �� <br />Nicole Egan <br />952-249-4625 <br />To schedule your inspections please call: (952) 249-4600 <br />CODE REQUIREMENTS ARE FOR YOUR PERSONAL HEALTH AND SAFETY! <br />