Laserfiche WebLink
Page 11 of 14 National Evaluation Report No. NER-520 <br /> Footnates for Racking Load Table <br /> Panels are made of two equal layers of APA or TECO rated OSB sheathing. The core shall be nominal 1.0 pcf density(min. <br /> 0.9 pcfl EPS (expanded polystyrene)foam adhered to the sheathing with glue and set under pressure. <br /> 1. Allowable load of 208 plf is based on using surface splines consisting of minimum 3 inch wide, 5/8 inch thick AD plywood <br /> at all panel edges, both sides. Panel skins shall be stapled to the splines using minimum 16 ga., 7/16 inch crown by 1-3/4 <br /> inch long staples along all panel edges at 6 inches on center, both sides. <br /> 2. Allowable load of 385 plf is based on using minimum 2x SPF solid sawn lumber splines at all panel edges. Panel skins shall <br /> be nailed to the splines using minimum 8d common nails along all panel edges at 6 inches on center, both sides. <br /> Footnotes for Transverse Loads Tables <br /> Panels shall be made of two equal layers of APA or TECO rated OSB sheathing.The core shall be nominal 1.0 pcf density <br /> (min. 0.9 pcfl EPS(expanded polystyrene)foam adhered to the sheathing with glue and set under pressure. In panels with <br /> spline studs,the skins shall be nailed to the spline studs with 6d nails @ 6 inches o.c.When the tables indicate that no spline <br /> studs are required for structural capacity, it is permitted to join adjacent panels using 3 inch (76.2 mm)wide, 5/8 inch (15.9 <br /> mm)thick plywood or OSB surface splines under the skins of each face instead of spline studs. The surface splines shall <br /> be installed using a gap filling expanding foam sealant and 1-1/4 inch (25.4 mm) long, No. 6 screws at 6 inches(152 mm) <br /> on center on each side of the joint. <br /> 1. Values shown are allowable spans due to dead load plus live load. <br /> 2. The tables reflect two deflection criteria. For all panels the deflection criteria of L/360 shall be used for floor loads. For roof <br /> panels with slopes less than 3 in 12 pitch,the L/360 deflection criterion shall be used. For roof panels with slopes of 3 in 12 <br /> or greater, the deflection criterion of L/240 shall be acceptable. <br /> 3. To minimize deflection creep on panels without splines loaded with permanent or long-duration loads (> 6 mo.), find the <br /> allowable span on the table for twice the actual load (i.e. use 40 psf for actual load of 20 psf.) <br /> 4. Some allowable spans are not based on deflections, therefore, no multipliers for other deflection criteria shall be allowed. <br /> 5. All values are for normal duration loads. No increases for other durations are allowed. <br /> 6. Maximum spans are limited to the maximum panel size, 28 feet. <br /> 7. All values listed are for single-span panels with supports at each end. <br /> 8. For eight foot wide panels with splines at 8'-0" o.c., use table values for sandwich panels without splines; for panels with <br /> splines at 4'-0"o.c., use tables for single splines. <br /> 9. All values are based on INSULSPAN -Transverse Load Tables (T.1 -T.38), "OINSULSPAN 1999", dated September 9, <br /> 1999. <br /> Footnotes for Axial Load Tables <br /> Panels shall be made of two equal layers of APA or TECO rated OSB sheathing.The core shall be nominal 1.0 pcf density <br /> (min. 0.9 pc� EPS(expanded polystyrene)foam adhered to the sheathing with glue and set under pressure. In panels with <br /> spline studs,the skins shall be nailed to the spline studs with 6d nails @ 6 inches o.c.When the tables indicate that no spline <br /> studs are required for structural capacity, it is permitted to join adjacent panels using 3 inch (76.2 mm)wide, 5/8 inch(15.9 <br /> mm)thick plywood or OSB surface splines under both exterior and interior skins instead of spline studs.The surface splines <br /> shall be installed using a gap filling expanding foam sealant and 1-1/4 inch (25.4 mm) long, No. 6 screws at 6 inches(152 <br /> mm)on center on each side of the joint <br /> 1. Values shown are allowable heights due to dead load plus live load. <br /> 2. Allowable loads are based on axial loads being applied over the entire panel width. <br /> 3. A deflection criterion of H/240 is used. <br /> 4. Some allowable spans are not based on deflections, therefore, no multipliers for other deflection criteria shall be allowed. <br /> 5. All values are for normal duration loads. No increases for other durations are allowed. <br /> 6. Maximum spans are limited to the maximum panel size, 28 feet <br /> 7. All values listed are for single-span panels with supports at the top and bottom. <br /> 8. Where no allowable height is shown, panel does not meet criteria to carry applied axial load. <br /> 9. For panels with splines at 24"o.c. use the allowable heights of panels with double splines. <br /> 10. For eight foot wide panels with splines at 8'-0"o.c., use table values for sandwich panels without splines; for panels with <br /> splines 4'-0"o.c., use tables for single splines. <br /> 11. All values are based on INSULSPAN -Axial Load Tables(A.1 -A.200), "OINSULSPAN 1999", dated September 9, 1999. <br /> 1_0 SUBJECT 3.0 DESCRIPTION 6_0 EVIDENCE SUBMITTED <br /> 2_0 PROPERTY FOR WHICH 4_0 INSTALLATION 7_0 CONDITIONS OF USE <br /> EVALUATION IS SOUGHT 5_0 IDENTIFICATION <br /> Re-Issued November 1, 2002 NES <br /> back to the NES home paqe National Evaluation Service, Inc. Product Evaluation Listinq <br /> Copyright0 2002 <br />