Laserfiche WebLink
Delta Treatment Systems • 9125 Comar Drive, Walker, LA 70785 • 1-800-219-9183 • www.deltatreatment.com12 <br />SPECIFICATIONS <br />ECOPOD-N Unit Specifications <br />Treatment <br />Plant <br />Treatment <br />Capacity (GPD) <br />Minimum Primary <br />Tank Total <br />Volume (Gal) <br />Reactor Tank <br />Volume <br />(Gal) <br />Reactor Tank <br />Dilution Volume <br />(Gal) <br />Media <br />Size <br />Air <br />Requirements <br />E50N 500 500 710 590 2'x2'x4'12 CFM <br />E60N 600 600 916 736 2'x2'x6'14.4 CFM <br />E75N 750 750 1090 910 2'x2'x6'18 CFM <br />E100N 1000 1000 1405 1165 2'x2'x8'24 CFM <br />E150N 1500 1500 2100 1740 2'x2'x6'36 CFM <br />MATERIALS OF CONSTRUCTION <br />Suffix FF Reactor Tank Fiberglass <br /> Cover Fiberglass <br /> Media Container Polyethylene <br />Suffix CA Reactor Tank Concrete <br /> Cover Concrete <br /> Media Container Polyethylene <br />Suffix IM Reactor Tank Polypropylene <br /> Cover Polypropylene <br /> Media Container Polyethylene <br />These are standard production units. Other configurations are available upon request. <br />ECOPOD-N Electrical Requirements <br />Model Compressor Motor Full Load Amps Measured Operating Watts Electrical Requirements <br />E50N Delta Model 06 3.5 185 115 volt – single phase <br />E60N Delta Model 06 4.7 280 115 volt – single phase <br />E75N Delta Model 06 4.7 280 115 volt – single phase <br />E100N Delta Model K03 7.1 475 115 volt – single phase <br />E150N Delta Model K03 7.1 475 115 volt – single phase <br />ECOPOD-N Reactor Tank Dimensions <br />Treatment Plant A B C D <br />E50N 47”44”54.7”127” <br />E60N 47”44”54.7”127” <br />E75N 47”44”54.7”127” <br />E100N 47”44”55”176” <br />E150N 47”44”55”176”