Laserfiche WebLink
MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES <br /> TABLE 2209.5.4.3.6(1) <br /> MAXIMUM RADIANT HEAT EXPOSURE t' <br /> EXPOSED OBJECT MAXIMUM RADIANT HEAT TIME DURATION(minutes) <br /> Personnel 1,500 Btu/hrft2(4732 W/m2) 3 <br /> Noncombustible e'uiment 8,000 Btu/hrft2(25 237 W/m2) Any <br /> Lot line 500 Btu/hrft2(1577 W/m2) Any <br /> TABLE 2209.5.4.3.6(2) <br /> MAXIMUM HYDROGEN CONCENTRATION EXPOSURE <br /> EXPOSED OBJECT MAXIMUM HYDROGEN CONCENTRATION <br /> Personnel,buildings or equipment 50%LFL within a distance of D and H of Table 2209.5.4.3.4 <br /> Lot line 50%LFL within 1.25 times the distance of D and H of Table 2209.5.4.3.4 <br /> 2210.2.1 Class I,II or IIIA liquid storage. Class I, II or 2210.3.5 Liquefied petroleum gas. Liquefied petroleum <br /> IIIA liquids stored inside of buildings used for marine motor gas cylinders shall not be filled at marine motor fuel-dis- <br /> fuel-dispensing facilities shall be stored in approved con- pensing facilities unless approved.Approved storage facili- <br /> tainers or portable tanks.Storage of Class I liquids shall not ties for LP-gas cylinders shall be provided.See also Section <br /> exceed 10 gallons(38 L). 2207. <br /> Exception: Storage in liquid storage rooms in accor- 2210.4 Fueling of marine vehicles at other than approved <br /> dance with Section 3404.3.7. marine motor fuel-dispensing facilities.Fueling of floating <br /> 2210.2.2 Class H or IIIA liquid storage and dispensing. marine craft with Class I fuels at other than a marine motor <br /> Class II or IIIA liquids stored or dispensed inside of build- fuel-dispensing facility is prohibited. Fueling of floating <br /> ings used for marine motor fuel-dispensing facilities shall marine craft with Class II or III fuels at other than a marine <br /> be stored in and dispensed from approved containers or por- motor fuel-dispensing facility shall be in accordance with all of <br /> table tanks. Storage of Class II and IIIA liquids shall not the following: <br /> exceed 120 gallons(454 L). 1. The premises and operations shall be approved by the <br /> 2210.2.3 Heating equipment.Heating equipment installed fire code official. <br /> in Class I,II or IIIA liquid storage or dispensing areas shall 2. Tank vehicles and fueling operations shall comply with <br /> comply with Section 2201.6. Section 3406.6. <br /> 2210.3 Dispensing.The dispensing of liquid fuels at marine 3. The dispensing nozzle shall be of the listed auto- <br /> motor fuel-dispensing facilities shall comply with Sections matic-closing type without a latch-open device. <br /> 2210.3.1 through 2210.3.5. <br /> 4. Nighttime deliveries shall only be made in lighted areas. <br /> 2210.3.1 General.Wharves,piers or floats at marine motor 5. The tank vehicle flasher lights shall be in operation while <br /> fuel-dispensing facilities shall be used exclusively for the <br /> dispensing or transfer of petroleum products to or from dispensing. <br /> marine craft,except that transfer of essential ship stores is 6. Fuel expansion space shall be left in each fuel tank to pre- <br /> allowed. vent overflow in the event of temperature increase. <br /> 2210.3.2 Supervision.Marine motor fuel-dispensing facil- 2210.5 Fire prevention regulations.General fire safety regu- <br /> ities shall have an attendant or supervisor who is fully aware lations for marine motor fuel-dispensing facilities shall comply <br /> of the operation,mechanics and hazards inherent to fueling with Sections 2210.5.1 through 2210.5.7. <br /> of boats on duty whenever the facility is open for business. 2210.5.1 Housekeeping. Marine motor fuel-dispensing <br /> The attendant's primary function shall be to supervise, facilities shall be maintained in a neat and orderly manner. <br /> observe and control the dispensing of Class I,II or IIIA liq- Accumulations of rubbish or waste oils in excessive <br /> uids or flammable gases. <br /> amounts shall be prohibited. <br /> 2210.3.3 Hoses and nozzles. Dispensing of Class I, II or <br /> IIIA liquids into the fuel tanks of marine craft shall be by 2210.5.2 Spills.Spills of Class I,II or IIIA liquids at or on <br /> means of an approved-type hose equipped with a listed the water shall be reported immediately to the fire depart- <br /> automatic-closing nozzle without a latch-open device. ment and jurisdictional authorities. <br /> Hoses used for dispensing or transferring Class I, II or 2210.5.3 Rubbish containers. Metal containers with <br /> IIIA liquids,when not in use,shall be reeled,racked or oth- tight-fitting or self-closing metal lids shall be provided for <br /> erwise protected from mechanical damage. the temporary storage of combustible trash or rubbish. <br /> 2210.3.4 Portable containers. Class I, II or IIIA liquids 2210.5.4 Marine vessels and craft. Vessels or craft shall <br /> shall not be dispensed into a portable container unless such not be made fast to fuel docks serving other vessels or craft <br /> container is approved. occupying a berth at a marine motor fuel-dispensing facility. <br /> 210 2006 INTERNATIONAL FIRE CODE® <br />