Laserfiche WebLink
SWIMMING POOL <br /> McGUIRE RESIDENCE 1 <br /> 1 HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES I <br /> ROOM: (SWIMMING POOL 1 j I HEIGHT: I 11 1 <br /> FLOOR 1 11 1 AREA: 1690 IVOLUME:1 18,590 <br /> OCCUPANTS: 0 1 i <br /> 1 'HEAT LOSS I <br /> ELEMENT AREA I X MULTIPLIER 1= BTU/HR <br /> ROOF 1690 1S.F I 2.2 Btu/Hr/S.FI j 3,718 ' <br /> DOORS 0 1" 57 " j I - <br /> WINDOWS 0 1" 57 " - <br /> WALLS 1 j 1,027 +1" 38 1 39,026 <br /> FOUNDATION i 360 1 7.51 " 1 2,700 <br /> INFILTRATION* 0 (CFM j 102.6 Btu/Hr/CFM 1 - 1 <br /> VENTILATION** 1500 (CFM 102.6,Btu/Hr/CFM 1 153,9001 <br /> TOTAL 1199,3441 <br /> 1 <br /> 1 HEAT GAIN f SENS. LATENT TOTAL <br /> ROOF 1 j 0 S.F. 0.92IBtu/Hr/S.F. ! - - <br /> DOORS l S&W 0 1" 1001 " 1 - - <br /> DOORS IN&E 0 91 - <br /> WINDOWS S&W 1 0 1" 1001 - i - <br /> WINDOWS N 0 F 91 " I - - <br /> WINDOWS E 0 1 601 " I - - <br /> WALLS 1S&W 0 1.91 " - - <br /> WALLS 1N 0 1" 0.81 " - - <br /> WALLS E 0 1 0.81 - - <br /> i <br /> LIGHTS 1 i 0 3.415 *** L - - <br /> EQUIPMENT 0 1KW 34151Btu/kw ! I - ! 1 - <br /> OCCUPANTS i 0 **** 300/3001 1 - - - <br /> INFILTRATION 0 CFH 0.3/0.41Btu/hr/CFH - - - <br /> VENTILATION 1,500 ,CFM 16/251Btu/hr/CFM 24,000 37,5001 61,500 <br /> j 1TOTAL: i 1 24,000 L 37,500 I 61,500 <br /> NOTES: <br /> Infiltration based on 1/2 CFM per lineal feet of crack 1 <br /> ***Lighting heat gain based on 1 watt per square foot <br /> **Ventilation based on 2 CFM per S.F. Bathroom or Laundry <br /> ****Occupants normally in continuous use of area <br /> Sensible and Latent load-based on light activity unless noted otherwise <br /> Page 1 <br />