<br /> Total Building Summary Loads
<br /> �:� _ '.as `�r"'x<T � '` .•'^rte*3 � ;,}s.���`' ��'-. f'
<br /> 4A-6-o: Glazing-Double pane low-e(er= 0.20 or less), 776 22,021 0 21,622 21,622
<br /> high performance, operable window, a=0.05 on
<br /> surface 2, any frame, outdoor insect screen with 50%
<br /> coverage, dark color blinds at 45°with 100%
<br /> coverage, u-value 0.33, SHGC 0.33
<br /> 11 N: Door-Metal-Polystyrene Core 64 1,927 0 761 761
<br /> 12E-Osw:Wall-Frame, R-19 insulation in 2 x 6 stud 3988.2 23,323 0 6,887 6,887
<br /> cavity, no board insulation, siding finish,wood studs
<br /> 15BO-10s3-8: Wall-Basement, , R-10 board insulation to 1774.5 10,578 0 684 684
<br /> 3', no interior finish, 8'floor depth
<br /> 16CR-44: Roof/Ceiling-Under Attic with Insulation on Attic 2559 4,842 0 2,704 2,704
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings),Vented Attic with Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal,Tar and Gravel or
<br /> Membrane, R-44 insulation
<br /> 21A-28: Floor-Basement, Concrete slab, any thickness, 2 2776 5,253 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 28'wide
<br /> Subtotals for structure: 67,944 0 32,658 32,658
<br /> People: 15 3,300 4,500 7,800
<br /> Equipment: 1,500 1,200 2,700
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 216, Summer CFM: 102 19,851 2,036 2,497 4,533
<br /> Ventilation: Winter CFM:240, Summer CFM: 240 22,028 4,797 5,891 10,688
<br /> Exhaust: Winter CFM: 200, Summer CFM: 200
<br /> AED Excursion: 0 0 4,093 4,093
<br /> Total Building Load Totals: 109,823 11,633 50,840 62,473
<br /> Total Building Supply CFM: 2,106 CFM Per Square ft.: 0.301
<br /> Square ft. of Room Area: 6,994 Square ft. Per Ton: 1,343
<br /> Volume(fP)of Cond. Space: 68,263
<br /> r` f_e ..
<br /> Total Heating Required Including Ventilation Air: 109,823 Btuh 109.823 MBH
<br /> Total Sensible Gain: 50,840 Btuh 81 %
<br /> Total Latent Gain: 11,633 Btuh 19 %
<br /> Total Cooling Required Including Ventilation Air: 62,473 Btuh 5.21 Tons(Based On Sensible+ Latent)
<br /> " _"� - � - r ---mac: •�' :: s�'^`-'� �-'�' - _ � "
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary:
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Nor-Son-Hamelot.rh9 Tuesday, January 03, 2017, 9:30 AM