Rhvac-Residential&Light Commercial HVAC Loads is Elite Software Development,Inc.
<br /> Sabre Plumbing&Heating 7800-Barlow
<br /> Plymouth.MN 55447 Page 4
<br /> Total Building Summary Loads
<br /> ..
<br /> Low EE: Glazing-LowEE Builder Grade .31 U-value, .29 454.8 12,262 0 11,417 11,417
<br /> SHGC, Window and Patio Door, u-value 0.31, SHGC
<br /> 0.29
<br /> 11J: Door-Metal - Fiberglass Core 41.8 2,181 0 602 602
<br /> 15A-15sffc-8:Wall-Basement, concrete block wall, R-15 1548 4,890 0 89 89
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 8'floor depth
<br /> 12F-Osw: Wall-Frame, R-21 insulation in 2 x 6 stud 2363.8 13,367 0 2,044 2,044
<br /> cavity, no board insulation, siding finish, wood studs
<br /> RJ 20 Spray Foam: Wall-Frame, Custom, Rim Joist R-20 347.5 1,512 0 424 424
<br /> Closed Cell Spray Foam
<br /> R49 16B-49: Roof/Ceiling-Under Attic with Insulation on 2464 4,930 0 2,720 2,720
<br /> Attic Floor(also use for Knee Walls and Partition
<br /> Ceilings), Custom, R-49 Blown Insulation, No
<br /> Radiant Barrier, Vented Attic, Asphalt Shingles
<br /> 21A-20: Floor-Basement, Concrete slab, any thickness, 2 2448 5,750 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 20'wide
<br /> Subtotals for structure: 44,892 0 17,296 17,296
<br /> People: 6 1,200 1,380 2,580
<br /> Equipment: 901 3,638 4,539
<br /> Lighting: 750 2,558 2,558
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> Ventilation: Winter CFM: 175, Summer CFM: 175 6,500 4,061 971 5,032
<br /> Humidification (Winter) 15.67 gal/day : 5,745 0 0 0
<br /> AED Excursion: 0 0 2,099 2,099
<br /> Total Building Load Totals: 57,137 6,162 27,942 34,104
<br /> a ; n
<br /> :1',-:
<br /> d . �cx#r,u ���x 3 .. . . . . ..."xi§� ti��a�= s.,.,144i:1-'4:0L--:,;4 7 ,:a;:
<br /> Total Building Supply CFM: 1,264 CFM Per Square ft.: 0.257
<br /> Square ft. of Room Area: 4,912 Square ft. Per Ton: 1,728
<br /> Volume (ft3)of Cond. Space: 46,672
<br /> :, a s .a ,w e,y':fiva.`t3e ial5:11 1,a`' n `.. , .. , ,.,,4 ., a dh'a10 ,rf°+ „y '1
<br /> Total Heating Required Including Ventilation Air: 57,137 Btuh 57.137 MBH
<br /> Total Sensible Gain: 27,942 Btuh 82 %
<br /> Total Latent Gain: 6,162 Btuh 18 %
<br /> Total Cooling Required Including Ventilation Air: 34,104 Btuh 2.84 Tons(Based On Sensible + Latent)
<br /> + ,: x ,- . . : , w,„,, ., , ,k.',..,,,,,,,,:- 1
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> Monday, May 16, 2016, 10:05 AM